background image

Operating instructions

W3G630-GD03-A1

Translation of the original operating instructions

3.5 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product drawing.

3.6 Transport and storage conditions

;

Use the device in accordance with its degree of protection.

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.7 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC circuit feedback

According to EN 61000-3-2/3

EMC interference
emission

According to EN 55022 (Class B,
household environment)

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing device
from packaging

Blades can bend
→ Carefully remove the device from its packaging, by the fan

housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
Heavy load when unpacking device

Risk of physical injury, such as back injuries.
→ Two people should work together to remove the device from

its packaging.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

Item no. 50431-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 6 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

[email protected]  

Содержание W3G630-GD03-A1

Страница 1: ...ed trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety ru...

Страница 2: ...omer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the d...

Страница 3: ...Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to d...

Страница 4: ...in mm 1 Direction of air flow V 2 Cable PVC AWG18 5x crimped ferrules 3 Cable PVC AWG22 3x crimped ferrules Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulfingen Gmb...

Страница 5: ...impeller combination in a standardized measurement setup 3 4 Technical description Weight 19 6 kg Fan size 630 mm Rotor surface Painted black Blade material Press fitted sheet steel blank sprayed wit...

Страница 6: ...undamaged device in accordance with your application CAUTION Possible damage to the device If the device slips during installation serious damage can result Ensure that the device is securely position...

Страница 7: ...a standstill and the line voltage is switched on The values are typically less than 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Res...

Страница 8: ...tructions Direction of action Positive heating Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax...

Страница 9: ...lure 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC red Voltage output 10 VDC...

Страница 10: ...n error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line...

Страница 11: ...an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecologi...

Страница 12: ...ectronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 12...