background image

Operating instructions

W3G630-GD03-A1

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-GF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed / min

-1

800

Power consumption / W

280

Current draw / A

1.2

Max. back pressure / Pa

75

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to ErP Directive

Actual

Req. 2015

01 Overall efficiency η

es

/ %

42.3

29.8

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

52.5

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

W3G630-GD03-A1

09 Power consumption P

ed

/ kW

0.24

09 Air flow q

v

/ m³/h

6570

09 Pressure increase total p

sf

/

Pa

52

10 Speed n / min

-1

805

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

19.6 kg

Fan size

630 mm

Rotor surface

Painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Fan housing material

Sheet steel, pre-galvanized and coated
with black plastic (RAL 9005)

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

"V"

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54; installation- and position-dependent

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

F3-1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Alarm relay
- Motor current limitation
- PFC, active
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1

Approval

EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

Item no. 50431-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

[email protected]  

Содержание W3G630-GD03-A1

Страница 1: ...ed trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety ru...

Страница 2: ...omer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the d...

Страница 3: ...Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to d...

Страница 4: ...in mm 1 Direction of air flow V 2 Cable PVC AWG18 5x crimped ferrules 3 Cable PVC AWG22 3x crimped ferrules Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulfingen Gmb...

Страница 5: ...impeller combination in a standardized measurement setup 3 4 Technical description Weight 19 6 kg Fan size 630 mm Rotor surface Painted black Blade material Press fitted sheet steel blank sprayed wit...

Страница 6: ...undamaged device in accordance with your application CAUTION Possible damage to the device If the device slips during installation serious damage can result Ensure that the device is securely position...

Страница 7: ...a standstill and the line voltage is switched on The values are typically less than 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Res...

Страница 8: ...tructions Direction of action Positive heating Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax...

Страница 9: ...lure 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC red Voltage output 10 VDC...

Страница 10: ...n error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line...

Страница 11: ...an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecologi...

Страница 12: ...ectronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50431 5 9970 ENU Change 89187 Approved 2016 04 15 Page 12...

Отзывы: