background image

Operating instructions

W3G300-ME46-01

Translation of the original operating instructions

4.4 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

10

2.3

+

Power 

11

2.4

-

Power supply -

12

2.2

0-10 V / PWM

Control input: Ri > 27 kΩ
0-10 V: (typ. 0.5 V -> Standby; 1.5 V -> n = min.; 9.5 V -> n = max.)
or PWM: (12 V - Ub; 1 kHz - 10 kHz; typ. < 1% -> standby; 10% -> n = min.; 95% -> n = max.)

13

2.1

DIAG

Diagnostic output: Open Collector, Isorce max = 10 mA, Rsource = 2 kΩ; Rsink = 100 kΩ
fan OK -> low; fan error -> high

Item no. 57879-5-9970 · ENU · Change 262216 · Approved 2022-09-19 · Page 7 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G300-ME46-01

Страница 1: ...packed installed operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test...

Страница 2: ...opriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant...

Страница 3: ...hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan...

Страница 4: ...2 4 GND Accessory part Cable 460 mm with mating connector part no 02040 4 1021 not included in scope of delivery 4 pole mating connector TE 1 1718628 1 2x plug contact TE 1 968857 1 2x plug contact TE...

Страница 5: ...lt in component with basic insulation protection class is based on the intended installation This component for installation may have several local protection classes This information relates to this...

Страница 6: ...s have been tightened The fan must not be strained on fastening 4 2 Electrical connection CAUTION Voltage The fan is a built in component and has no disconnecting switch Only connect the fan to circui...

Страница 7: ...t Ri 27 k 0 10 V typ 0 5 V Standby 1 5 V n min 9 5 V n max or PWM 12 V Ub 1 kHz 10 kHz typ 1 standby 10 n min 95 n max 13 2 1 DIAG Diagnostic output Open Collector Isorce max 10 mA Rsource 2 k Rsink 1...

Страница 8: ...not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs...

Страница 9: ...every 6 months Replace device Abnormal bearing noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority cor...

Страница 10: ...r internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 578...

Отзывы: