Operating instructions

8300100104

VBH0310CTRLS

Translation of the original operating instructions

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Device malfunctions possible

Route the device's control lines separately from the supply line.
→ Maintain the greatest possible clearance.

Recommendation: clearance > 10 cm (separate cable
routing)

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 61800-5-1

Compliance with the resistance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device. The protective earth
terminal is located on the housing and provided with a protective earth
symbol and a hole.

4.2.2 Supply connection and fuses

Assignment of supply cable cross-sections and their required fuses (line
protection only, no equipment protection).

Nominal
voltage

Fuse

Automatic
circuit
breaker

Cable
cross-
section

Cable
cross-
section

VDE

UL

VDE

mm²

*AWG

3/PE AC
380-480
VAC

16 A

15 A

C16A

1.5

16

3/PE AC
380-480
VAC

20 A

20 A

C20A

2.5

14

3/PE AC
380-480
VAC

25 A

25 A

C25A

4.0

12

* AWG = American Wire Gauge

4.2.3 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 5 W.

Item no. 1170000606 · ENU · Change 0 · Approved 2021-12-16 · Page 7 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание VBH0310CTRLS

Страница 1: ...device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again f...

Страница 2: ...tact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected...

Страница 3: ...hapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the...

Страница 4: ...Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k...

Страница 5: ...er air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulati...

Страница 6: ...arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected...

Страница 7: ...ts Check whether the information on the nameplate matches the connection data Before connecting the device make sure the power supply matches the device voltage Only use cables designed for the curren...

Страница 8: ...the cable used This must be checked by the user Fig 2 Recommended stripped lengths inside terminal box 1 supply line 2 control and relay line 4 3 2 Terminal connection data Supply line min max Rigid...

Страница 9: ...htening torque 3 5 0 4 Nm Connect the cables to the corresponding terminals Use a screwdriver to do so When connecting make sure the wires do not splay out Insert the strands until they meet with resi...

Страница 10: ...characteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic cur...

Страница 11: ...C SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3...

Страница 12: ...riginal operating instructions 4 6 Equivalent circuit diagrams Item no 1170000606 ENU Change 0 Approved 2021 12 16 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 79...

Страница 13: ...8 1 Suppression of speed ranges Speed ranges in which the vibration velocity in the motor fan is too high must be avoided in continuous operation Excessive vibration velocities can be caused by reson...

Страница 14: ...starts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the de...

Страница 15: ...astening diameter on the motor support plate in the direction of the motor axis of rotation and perpendicular to this Fig 6 Example illustrating vibration measurement The arrangement of the sensors de...

Страница 16: ...mendations for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific l...

Отзывы: