Operating instructions

S4D500-AM01-03

Translation of the original operating instructions

Fig. 3: Cable routing for fans installed upright.

4.3.4 Motor protection

CAUTION
Voltage

The device is a built-in component with no isolating switch.
→ Connect the device to a suitable tripping device.
→ Only connect the device to circuits which can be de-

energised with an all-pole disconnection switch.

→ When working on the device, the system/machine in

which the device is installed must be secured so as to
prevent it from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect up the thermal overload protector installed in the coil.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect up the thermal overload protector correctly will
invalidate your warranty claim.

Item no. 11295-5-9970 · Revision 82543 · Release 2014-05-08 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4D500-AM01-03

Страница 1: ...nly authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety haz...

Страница 2: ...ng hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect...

Страница 3: ...se hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations M...

Страница 4: ...ve the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 4 11...

Страница 5: ...Power input Pe kW 0 66 Air flow qv m h 5985 Pressure increase total psf Pa 134 Speed n min 1 1355 Data definition with optimum efficiency The ErP data is determined using a motor impeller combination...

Страница 6: ...necting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury f...

Страница 7: ...equency inverter Please use a frequency converter only after consultation with ebm papst When a frequency converter is used for speed adjustment the maximum safe operating speed see 3 2 Nominal data m...

Страница 8: ...o prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil...

Страница 9: ...ction Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 9 11 ebm papst Mulfingen...

Страница 10: ...that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use includ...

Страница 11: ...on diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overte...

Отзывы: