Operating instructions

S4D500-AM01-03

Translation of the original operating instructions

4.5 Open additional screwed cable glands

You have the ability to break a second cable gland opening through on
the terminal box.

WARNING
In event of a fault, the screwed cable gland is under
electrical voltage

Electric shock
→ Do not use metal cable glands for plastic terminal

boxes.

;

Screw the cable gland into the pre-cut thread using a screwdriver.
When doing so, note the tightening torques, see chapter 3.1 Product
drawing.

;

Remove the plastic tab that falls off when the wire is pressed through
into the terminal box.

Fig. 4: Screwed cable gland opening

4.6 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

;

Screw the terminal box cover closed again. Terminal box tightening
torque, see chapter 3.1 Product drawing.

;

Make sure that the terminal box is correctly closed and sealed and
that all screws and screwed cable glands are properly tightened.

4.7 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

4.8 Switching off the device

;

Disconnect the device from the supply voltage at the main switch for
the supply line.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

Item no. 11295-5-9970 · Revision 82543 · Release 2014-05-08 · Page 10 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4D500-AM01-03

Страница 1: ...nly authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety haz...

Страница 2: ...ng hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect...

Страница 3: ...se hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations M...

Страница 4: ...ve the unit mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 4 11...

Страница 5: ...Power input Pe kW 0 66 Air flow qv m h 5985 Pressure increase total psf Pa 134 Speed n min 1 1355 Data definition with optimum efficiency The ErP data is determined using a motor impeller combination...

Страница 6: ...necting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury f...

Страница 7: ...equency inverter Please use a frequency converter only after consultation with ebm papst When a frequency converter is used for speed adjustment the maximum safe operating speed see 3 2 Nominal data m...

Страница 8: ...o prevent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil...

Страница 9: ...ction Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11295 5 9970 Revision 82543 Release 2014 05 08 Page 9 11 ebm papst Mulfingen...

Страница 10: ...that all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use includ...

Страница 11: ...on diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overte...

Отзывы: