background image

Operating instructions

S4D400-AP12-35

Translation of the original operating instructions

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the fan
from the packaging

→ Carefully remove the device from its packaging, only

touching the guard grille. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check whether the data on the type plate agree with the connection
data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

4.2.2 Voltage control

With open loop speed control using transformers or electronic
voltage regulators (e.g. phase angle control), excessive current
may occur.
In addition, noises can occur with phase angle control
depending on the mounting situation.

4.2.3 Frequency inverter

Fit sinusoidal filters that work on all poles (live-live and live-
earth) between the frequency inverter and the motor for
operation with frequency inverters.
Depending on how the device is installed, noises may occur.

4.3 Connection in terminal box

4.3.1 Preparing connection lines for the connection

Strip the cable just enough so that the screwed cable gland is tight and
the terminals are relieved of strain. Tightening torque, see chapter 3.1
Product drawing.

4.3.2 Connecting cables with terminals

;

Remove the cap from the screwed cable gland.

Remove the cap only in those places where cables are inserted.

;

Insert the line(s) (not included in the standard scope of delivery) into
the terminal box.

;

First connect the "PE" (protective earth) connection.

;

Connect the lines to the corresponding terminals.

;

Connect the thermal overload protector (TOP).

Use a screwdriver to do so.
During the connection work, ensure that no cables splice off.

;

Seal the terminal box.

Item no. 11971-5-9970 · Revision 75470 · Release 2011-11-14 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4D400-AP12-35

Страница 1: ... personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the ap...

Страница 2: ... into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating p...

Страница 3: ...s particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning ...

Страница 4: ...s have the unit mm 1 Direction of air flow V 2 Tightening torque 0 7 0 2 Nm 3 Cable diameter max 7 5 mm tightening torque 1 3 0 2 Nm Item no 11971 5 9970 Revision 75470 Release 2011 11 14 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...r of blades 5 Direction of air flow V Direction of rotation Counter clockwise seen on rotor Type of protection IP 44 Depending on installation and position as per EN 60034 5 Insulation class B Humidity class F2 2 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 6099...

Страница 6: ...rcuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in acc...

Страница 7: ...itable trigger device Connect the device only to circuits that can be switched off using an all pole disconnecting switch When working on the device you must switch off the system machine in which the device is installed and secure it from being switched on again NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protecto...

Страница 8: ...nection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11971 5 9970 Revision 75470 Release 2011 11 14 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 9: ... repairs may be carried out by ebm papst only The terminal box does not have to be opened for maintenance Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION Th...

Страница 10: ...spection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Tightness of screwed cable gland Visual inspection At least every 6 mont...