background image

Operating instructions

S4D350-AA06-19

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND NOTES

1

1. SAFETY REGULATIONS AND NOTES

Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.

1.1 Levels of hazard warnings

1

1.1 Levels of hazard warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.

WARNING

Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualification

1

1.2 Staff qualification

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by trained and authorised technical staff.
Only authorised specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:
; Do not make any modifications, additions or conversions to the

device without the approval of ebm-papst.

1.4 Electrical voltage

1

1.4 Electrical voltage

; Check the electrical equipment of the device at regular intervals, refer

to chapter 5.2 Safety test.

; Replace loose connections and defective cables immediately.

DANGER

Electrical load on the device

Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically

charged device.

WARNING

Terminals and connections have voltage even with a

unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

2

1.5 Safety and protective functions

2

1.6 Mechanical movement

2

1.7 Emission

2

1.8 Hot surface

2

1.9 Transport

2

1.10 Storage

2

1.11 Disposal

3

2. PROPER USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Data according to ErP directive

5

3.4 Technical features

5

3.5 Mounting data

5

3.6 Transport and storage conditions

6

4. CONNECTION AND START-UP

6

4.1 Connecting the mechanical system

6

4.2 Connecting the electrical system

6

4.3 Connection in terminal box

8

4.4 Connection screen

9

4.5 Open additional screwed cable glands

9

4.6 Checking the connections

9

4.7 Switch on device

9

4.8 Switching off the device

9

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE

CAUSES AND REMEDIES

10

5.1 Cleaning

10

5.2 Safety test

Item no. 13971-5-9970 · Revision 82464 · Release 2014-02-21 · Page 1 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4D350-AA06-19

Страница 1: ...y authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the dev...

Страница 2: ...ong hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take...

Страница 3: ...sing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that ...

Страница 4: ...have the unit mm 1 Direction of air flow A 2 Tightening torque 1 3 0 2 Nm 3 Cable diameter min 6 mm max 8 mm tightening torque 2 0 3Nm Item no 13971 5 9970 Revision 82464 Release 2014 02 21 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...al of guard grille Steel coated in black plastic RAL9005 Number of blades 5 Direction of air flow A Direction of rotation Clockwise seen on rotor Type of protection IP 44 Depending on installation and position as per EN 60034 5 Insulation class B Humidity class F1 2 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mode S1...

Страница 6: ... data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 1...

Страница 7: ...e bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection CAUTION Voltage The device is a built in component with no isolating switch Connect the device to a suitable tripping device Only connect the device to circuits which can be de energised with an all pole disconnection switch When working on the device the system machine in whic...

Страница 8: ...Y Star connection L1 black L2 blue L3 brown U1 black V1 blue W1 brown U2 green V2 white W2 yellow TOP 2xgrey PE green yellow Item no 13971 5 9970 Revision 82464 Release 2014 02 21 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 9: ...tion last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION The motor restarts automatically when oper...

Страница 10: ...hs Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least eve...