Operating instructions

S4D350-AA06-19

Translation of the original operating instructions

4.5 Open additional screwed cable glands

You have the ability to open another cable gland opening on the terminal
box. To do so, remove the plug screw on the cable gland opening and
turn the screwed cable gland into the prefabricated thread using a
spanner. When doing so, note the tightening torques, see chapter 3.1
Product drawing.

4.6 Checking the connections

; Make sure that the power is off (all phases).
; Secure it from being switched on again.
; Check the correct fit of the connection lines.
; Screw the terminal box cover closed again. Terminal box tightening

torque, see chapter 3.1 Product drawing.

; Make sure that the terminal box is correctly closed and sealed and

that all screws and screwed cable glands are properly tightened.

4.7 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING

Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

; Inspect the device for visible external damage and the proper function

of the protective features before switching it on.

; Check the air flow paths of the fan for foreign objects and remove any

that are found.

; Apply the nominal voltage to the voltage supply.

4.8 Switching off the device

; Disconnect the device from the supply voltage at the main switch for

the supply line.

; When disconnecting, be sure to disconnect the earth wire connection

last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING

Terminals and connections have voltage even with a

unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION

The motor restarts automatically when operating voltage

is applied, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ Insert the brought-out thermal overload protector into the

control circuit so that the cooled off motor does not switch on
independently after a fault.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Unacceptable
operating point

Check operating point

Item no. 13971-5-9970 · Revision 82464 · Release 2014-02-21 · Page 9 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4D350-AA06-19

Страница 1: ...y authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the dev...

Страница 2: ...ong hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take...

Страница 3: ...sing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that ...

Страница 4: ...have the unit mm 1 Direction of air flow A 2 Tightening torque 1 3 0 2 Nm 3 Cable diameter min 6 mm max 8 mm tightening torque 2 0 3Nm Item no 13971 5 9970 Revision 82464 Release 2014 02 21 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...al of guard grille Steel coated in black plastic RAL9005 Number of blades 5 Direction of air flow A Direction of rotation Clockwise seen on rotor Type of protection IP 44 Depending on installation and position as per EN 60034 5 Insulation class B Humidity class F1 2 Mounting position Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes Rotor side Operation mode S1...

Страница 6: ... data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 1...

Страница 7: ...e bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection CAUTION Voltage The device is a built in component with no isolating switch Connect the device to a suitable tripping device Only connect the device to circuits which can be de energised with an all pole disconnection switch When working on the device the system machine in whic...

Страница 8: ...Y Star connection L1 black L2 blue L3 brown U1 black V1 blue W1 brown U2 green V2 white W2 yellow TOP 2xgrey PE green yellow Item no 13971 5 9970 Revision 82464 Release 2014 02 21 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 9: ...tion last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION The motor restarts automatically when oper...

Страница 10: ...hs Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least eve...

Отзывы: