3.2 Nominal data

Motor

M3G150-NA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

920

Power input / W

2800

Current draw / A

4.3

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

66.2

56.2

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

72

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

R3G710-AP02-01

09 Power input P

ed

/ kW

2.79

09 Air flow q

v

/ m³/h

13805

09 Pressure increase total p

sf

/

Pa

456

10 Speed (rpm) n / min

-1

920

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

44 kg

Size

710 mm

Motor size

150

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP55

Insulation class

"F"

Humidity (F) /
environmental
protection class (H)

H1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CSA C22.2 no. 77 + CAN/CSA-
E60730-1; EAC; UL 1004-7 + 60730-1

Item no. 52489-5-9970 · ENG · Revision 209539 · Release 2021-02-01 · Page 5 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G710-AP02-01

Страница 1: ...rry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidiness in the working area increases the risk of ...

Страница 2: ...until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk of injury Do not wear any loose fitting...

Страница 3: ...ing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in fl...

Страница 4: ... 2 4013 with pressure tap not included in scope of delivery 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 52489 5 9970 ENG Revision 209539 Release 2021 02 01 Page 4 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ... with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 44 kg Size 710 mm Motor size 150 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Material of impeller Aluminium sheet Number of blades 7 Direction of rotation Clockwise seen on rotor Type of protection IP5...

Страница 6: ...device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND START UP 4 1 Connecting the mechanical system CAUTION Cutting and crushing hazard when removing the fan from the packaging Carefully hold the impeller to remove the device from its packaging Make sure to avoid any shock Wear safety shoes an...

Страница 7: ...nment of conductor cross sections and the fuse protection required for them overload protection only no device protection Nominal voltage Safety fuse Automatic circuit breaker Wire cross section Wire cross section VDE UL VDE mm AWG 3 PE AC 380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 AWG American Wire Gauge 4 2 3 Idle current...

Страница 8: ...a screwdriver to do so During the connection work ensure that no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the consta...

Страница 9: ...g Control mode parameter set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function parameter set 2 Positive heating Item no 52489 5 9970 ENG Revision 209539 Release 2021 02 01 Page 9 15 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938...

Страница 10: ...contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS 485 RSA MODBUS RTU SELV KL 3 2 RSB Bus connection RS 485 RSB MODBUS RTU SELV KL 3 3 10 GND Signal ground for control interface SELV KL 3 4 Ain1 U Analogue input 1 set value 0 10 V Ri 100 kΩ parametrisable curve only usable as alternativ...

Страница 11: ...OM setting the controller function of the integrated controller is normally inversely selectable per bus or per digital input Din 3 normal open pin or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC SELV KL 3 11 Ain2 U Analogue input 2 actual value 0 10 V Ri 100 kΩ parametrisable curve only usable as alternative to input Ain2 SELV KL 3 12 20 V Fixed voltage output 20 VDC 20...

Страница 12: ...ance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature failure The maximum vibration severity may not exceed 3 5 mm s and should be checked every 6 months It must be measured at least in and perpendicular to the axial direction at the place where the mot...

Страница 13: ...ff de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the device cool...

Страница 14: ... this period Adapt the maintenance intervals to the dust pollution occurring 6 3 Safety test NOTE High voltage test The integrated EMC filter contains Y capacitors Therefore the trigger current is exceeded when AC testing voltage is applied Test the device with DC voltage when you carry out the high voltage test required by law The voltage to be used corresponds to the peak value of the AC voltage...

Страница 15: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminium Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets ...

Отзывы: