Operating instructions

R3G630-AB06-03

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

PE

PE

Protective earth terminal

KL1

1, 2, 3

L1, L2, L3

Power supply 50/60 Hz

KL2

1

NC

Floating status contact, break for failure

KL2

2

COM

floating status contact, changeover contact, common connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

KL2

3

NO

Floating status contact, make for failure

KL3

1

OUT

Analog output, 0-10 VDC, max. 3 mA, SELV,
output of current motor modulation level:
1 V corresponds to 10 % modulation level.
10 V corresponds to 100 % modulation level.

KL3

2, 8

GND

Reference ground for control interface, SELV

KL3

3, 7

0-10 V

Use control / current sensor value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input,
SELV

KL3

4

+10 V

Voltage output 10 VDC (±3 %), max. 10 mA, power supply for external devices
(e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25% / -10%), max. 50 mA, power supply for external devices
(e.g. sensors); SELV

KL3

6

4-20 mA

Use control / current sensor value input 4-20 mA, impedance 100 Ω only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for ebmBUS, RSB, SELV

KL3

10, 12

RSA

RS485 interface for ebmBUS, RSA, SELV

Item no. 50242-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 10 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G630-AB06-03

Страница 1: ...y suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product Note the following when working on the d...

Страница 2: ...fy that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be...

Страница 3: ...ce in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sustaining or life support function Operation with external vibrations Conveying solids in the flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box duri...

Страница 4: ...70 2 4013 not included in scope of delivery 2 Max clearance for screw 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50242 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ... All dimensions in mm Inlet ring 63070 2 4013 not included in scope of delivery Item no 50242 5 9970 ENU Change 89187 Approved 2016 04 15 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 6: ...using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 29 kg Fan size 630 mm Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material Sheet aluminum Number of blades 6 Direction of rotation Clockwise viewed toward rotor Degree of protection IP55 Insulation class F Moisture F Environmental H protection class F4 1 I...

Страница 7: ...ty shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to remove the device from its packaging Check the device for transport damage Damaged devices are not to be installed Install the undamaged device in accordance with your application CAUTION Possible damage to the device If the device slips...

Страница 8: ...A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standst...

Страница 9: ...do so When connecting ensure that no wire ends fan out Fig 2 Connecting wires to terminals Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable When routing the cable make sure that the cable glands are located at the bottom The cables must always be routed downward Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factor...

Страница 10: ...evel KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Use control current sensor value input 0 10 VDC impedance 100 kΩ only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometer SELV KL3 5 20 V Voltage output 20 VDC 25 10 max 50 mA power supply for external devices e g sensors SELV KL3 6 4 20 mA U...

Страница 11: ...d protective functions cause the motor to switch off automatically in the event of the faults described in the table The status relay drops out and the fault is reported via bus Fault Safety feature description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of p...

Страница 12: ...gh voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of the AC voltage required by the standard What to check How to check How often What action Contact protection cover for intactness ...

Страница 13: ...etallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets a...

Отзывы: