Operating instructions

R3G500-DA25-05

Translation of the original operating instructions

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; EAC; UL 1004-7 + 60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.5 Mounting data

Further mounting data can be taken from the product drawing or Chapter
4.1 Mechanical connection as required.

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.7 Electromagnetic compatibility

If several devices are connected in parallel on the supply side
so that the line current of the arrangement is in the range 16 - 75
A, this arrangement conforms to IEC 61000-3-12, provided that
the short-circuit power S

sc at the connection point of the

customer system to the public power grid is greater than or
equal to 250 times the rated output of the arrangement. It is the
responsibility of the installation engineer or operator/owner of the
device to ensure, if necessary after consultation with the
network operator, that this device is only connected to a
connection point with an S

sc value greater than or equal to 250

times the rated output of the arrangement.

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing fan from
packaging

→ Carefully remove the device from its packaging, by the fan

impeller. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

Содержание R3G500- DA25-05

Страница 1: ...199 1 8 017 399 83 88 E mail 5 v klapan by v klapan by EC Ebmpapst R3G500 DA25 05...

Страница 2: ...otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electric...

Страница 3: ...is possible e g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOT...

Страница 4: ...ce is to be used in networks with network quality characteristics as per EN 50160 Using the device only in stationary systems Performing all maintenance work Conveying air at an ambient air pressure b...

Страница 5: ...g instructions 3 TECHNICAL DATA 3 1 Product drawing All dimensions in mm 1 Accessory part inlet ring 63072 2 4013 not included in scope of delivery 2 Max clearance for screw 20 mm 3 Cable diameter min...

Страница 6: ...Operating instructions R3G500 DA25 05 Translation of the original operating instructions All dimensions in mm Inlet ring 63072 2 4013...

Страница 7: ...other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regu...

Страница 8: ...rrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected...

Страница 9: ...mbol and a hole 4 2 2 Supply connection and fuses Assignment of supply cable cross sections and their required fuses line protection only no equipment protection Nominal voltage Fuse Automatic circuit...

Страница 10: ...rdance with DIN 46228 1 for flexible cable 0 25 mm 1 5 mm NOTE Crimping and pressing forms of the wire end ferrules For flexible control and relay cables from a cable cross section of 1 0 mm a trapezo...

Страница 11: ...nd along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of wa...

Страница 12: ...Analog input 0 10 V PWM Ri 100 k function Set value Characteristic curve parameterizable see input characteristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions ta...

Страница 13: ...e high digital input not active pin open or applied voltage 1 5VDC active applied voltage 3 5 50VDC SELV D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k...

Страница 14: ...Operating instructions R3G500 DA25 05 Translation of the original operating instructions 4 7 Equivalent circuit diagrams...

Страница 15: ...igh vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find ano...

Страница 16: ...Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see con...

Страница 17: ...ation and perpendicular to this Fig 5 Example illustrating vibration measurement The arrangement of the sensors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a...

Страница 18: ...f the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard...