background image

Operating instructions

R3G310-PT08-J1

Translation of the original operating instructions

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of a fault, the rotor and the impeller will be
energized

The rotor and the impeller have basic insulation.
→ Do not touch the rotor and impeller once installed.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

1.5 Safety and protective features

DANGER
Guard missing and guard not functioning

Without a guard, hands may become caught up in the device
during operation for example, resulting in serious injury. Loose
parts or items of clothing could be drawn in.
→ The device is a built-in component. As the owner, you are

responsible for ensuring that the device is adequately
safeguarded.# Operate the device only with a fixed
protective device and guard grill.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open- and closed-loop control devices.
If impermissible radiation levels occur following installation, appropriate
shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interference after installing
the device in customer equipment.

→ Verify that the entire setup is EMC-compliant.

1.7 Mechanical movement

DANGER
Rotating device

Risk of injury to body parts coming into contact with the rotor or
the impeller.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair and dangling items of clothing, jewelry and the like
can become entangled and be pulled into the device. Injuries
can result.
→ Do not wear any loose-fitting or dangling clothing or jewelry

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emissions

WARNING
Depending on the installation and operating conditions,
the sound pressure level may exceed 70 dB(A).

Risk of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment such as hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature on electronics housing

Risk of burns
→ Ensure sufficient protection against accidental contact.

1.10 Transport

WARNING
Transporting the fan

Injuries from tipping or slipping, damage to the fan
→ Always transport the fan with care and in its original

packaging. #Impact, e.g. if set down too hard or at an angle,
can lead to bearing damage or impeller deformations. #It
must be ensured that the fans cannot tip over during
transportation and handling. #Secure the fan(s) e.g. with a
lashing strip to stop anything slipping or tipping.

1.11 Storage

;

Store the device, partially or fully assembled, in a dry place,
protected against the weather and free from vibration, in the original
packaging in a clean environment.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and the longest possible
service life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
Chapter 3.6 Transport and storage conditions.

;

Make sure that all cable glands are fitted with dummy plugs.

Item no. 54673-5-9970 · ENU · Change 260745 · Approved 2022-07-08 · Page 2 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G310-PT08-J1

Страница 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Страница 2: ...accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become...

Страница 3: ...use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operat...

Страница 4: ...torque 1 8 0 3 Nm use must be made of seal provided Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 4 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use must be made of...

Страница 5: ...n mm Inlet ring 31475 2 4013 with pressure tap k factor 116 not included in scope of delivery Item no 54673 5 9970 ENU Change 260745 Approved 2022 07 08 Page 5 14 ebm papst Mulfingen GmbH Co KG Bachm...

Страница 6: ...ation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Ar...

Страница 7: ...r equal to 250 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the networ...

Страница 8: ...al protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol a...

Страница 9: ...s the cable glands 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if...

Страница 10: ...C1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 8 GND Reference ground for control interface SELV 9 RSA RS485 interface for MODBUS RSA SELV 10 RSB RS48...

Страница 11: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 12: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Страница 13: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Страница 14: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Отзывы: