Notes on surface quality
The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may vary during the production period.
Strength, dimensional stability and dimensional accuracy are not affected
by this.
The colour pigments of the paints used react perceptibly to UV light over
the course of time. This does not however have any influence on the
technical properties of the products. To prevent the formation of patches
and fading, the product is to be protected against UV radiation. Changes
in colour are not a reason for complaint and are not covered by the
warranty.
3.5 Mounting data
;
Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
Any further mounting data required can be taken from the product
drawing or Section chapter 4.1 Connecting the mechanical system.
3.6 Transport and storage conditions
Max. permissible
ambient motor temp.
(transp./ storage)
+80 °C
Min. permissible
ambient motor temp.
(transp./storage)
-40 °C
3.7 Electromagnetic compatibility
EMC interference
immunity
Acc. to EN 61000-6-2 (industrial
environment)
EMC harmonics
Acc. to EN 61000-3-2/3
EMC interference
emission
Acc. to EN 55022 (Class B, household
environment)
4. CONNECTION AND START-UP
4.1 Connecting the mechanical system
CAUTION
Cutting and crushing hazard when removing the fan
from the packaging
→ Carefully hold the impeller to remove the device from its
packaging. Make sure to avoid any shock.
→ Wear safety shoes and cut-resistant safety gloves.
NOTE
Damage to device from vibration
Bearing damage, reduced service life
→ Forces or impermissibly high vibration levels must not be
transmitted to the fan from system components.
→ If the fan is connected to air ducts, it should isolated from
vibrations, for example using compensators or similar
elements.
→ Fasten the fan to the substructure without distorting it.
;
Check the device for transport damage. Damaged devices must no
longer be installed.
;
Install the undamaged device according to your application.
CAUTION
Possibility of damage to the device
Serious damage may result if the device slips during assembly.
→ Keep the device fixed in position at the installation location
until all attachment screws have been tightened.
●
The fan must not be strained on fastening.
4.2 Connecting the electrical system
DANGER
Electric voltage on the device
Electric shock
→ Always install a protective earth first.
→ Check the protective earth.
DANGER
Incorrect insulation
Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
→ Route cables such that they cannot be touched by any
rotating parts.
CAUTION
Electrical voltage
The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with
an all-pole separating switch.
→ When working on the fan, you must switch off the
installation/machine in which the fan is installed and secure it
from being switched on again.
NOTE
Water penetration into leads or wires
Water enters at the cable end on the customers side and can
damage the device.
Item no. 50478-5-9970 · ENG · Revision 204653 · Release 2020-02-08 · Page 6 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com