background image

Operating instructions

R3G250-AV29-B1

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-FA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

3450

Power input / W

750

Current draw / A

3.3

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

58.9

50

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

70.9

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

R3G250-AV29-B1

09 Power input P

ed

/ kW

0.72

09 Air flow q

v

/ m³/h

1975

09 Pressure increase total p

sf

/

Pa

708

10 Speed (rpm) n / min

-1

3480

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

5.6 kg

Size

250 mm

Motor size

84

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP54

Insulation class

"B"

Humidity (F) /
environmental
protection class (H)

H1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Motor current limit
- PFC, active
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CCC; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

;

Use the device in accordance with its protection type.

Item no. 50478-5-9970 · ENG · Revision 204653 · Release 2020-02-08 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G250-AV29-B1

Страница 1: ...ry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is install...

Страница 2: ...Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against acc...

Страница 3: ...Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system...

Страница 4: ...ction for pressure relief k factor 70 not included in the standard scope of delivery 2 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 3 Depth of screw max 16 mm 4 Tightening torque 3 5...

Страница 5: ...termined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 6 kg Size 250 mm Motor size 84 Surface of rotor Coated in black Material of electr...

Страница 6: ...mage to device from vibration Bearing damage reduced service life Forces or impermissibly high vibration levels must not be transmitted to the fan from system components If the fan is connected to air...

Страница 7: ...D is required in your installation only universal residual current devices type B or B are permissible Residual current devices RCD cannot provide personal safety while operating the device as is also...

Страница 8: ...front of the cable gland for example When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans ins...

Страница 9: ...correspond to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA...

Страница 10: ...and off via power supply Switching off the device for maintenance work Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconne...

Страница 11: ...housing could lead to overheating of the motor Dirt on the impeller can cause vibration which would shorten the service life of the fan Severe vibration could destroy the fan In such cases immediatel...

Страница 12: ...phases of the life cycle The corresponding disposal standards are also to be heeded 6 4 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropr...

Отзывы: