background image

Operating instructions

R1G225-AF11-14

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Accessory part: inlet ring 96358-2-4013 not included in scope of delivery

2

Max. clearance for screw 6 mm

3

Cable PVC AWG20 with 4-pole connector housing AMP 207571-1

3.1

UN +48 VDC (red)

3.2

GND (blue)

3.3

PWM (black)

3.4

Fan good / fan bad (white)

Item no. 53155-5-9970 · ENU · Change 202598 · Approved 2020-01-07 · Page 4 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R1G225-AF11-14

Страница 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Страница 2: ...tact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and...

Страница 3: ...hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan...

Страница 4: ...ed in scope of delivery 2 Max clearance for screw 6 mm 3 Cable PVC AWG20 with 4 pole connector housing AMP 207571 1 3 1 UN 48 VDC red 3 2 GND blue 3 3 PWM black 3 4 Fan good fan bad white Item no 5315...

Страница 5: ...e in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may change during...

Страница 6: ...ecting switch Only connect the fan to circuits that can be switched off with an all pole disconnection switch When working on the fan secure the system machine in which the fan is installed so as to p...

Страница 7: ...y 48 VDC maximum ripple 3 5 1 2 PWM black PWM control input 1 3 Tach white Fan good fan bad evaluation n 1510 rpm high fan bad n 1620 rpm low fan good Isink max 10 mA 1 4 GND blue Reference ground Ite...

Страница 8: ...enance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply 5 MAINTENANCE MALFUNCTIONS PO...

Страница 9: ...noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmenta...

Страница 10: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 53155 5 9970 ENU Change 202598 Approved 2020 01...

Отзывы: