Operating instructions

M3G084-GF06-42

Translation of the original operating instructions

4. CONNECTION AND STARTUP

4.1 Mechanical connection

WARNING
Hot motor housing

Risk of fire
→ Ensure that no combustible or flammable materials are

located close to the motor.

CAUTION
Cutting and crushing hazard when removing motor from
packaging

→ Carefully remove the device from its packaging. Strictly

avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The motor is a built-in component and has no disconnecting
switch.
→ Only connect the motor to circuits that can be switched off

with an all-pole disconnection switch.

→ When working on the motor, secure the system/machine

in which the motor is installed so as to prevent it from being
switched back on.

NOTE
Device malfunctions possible

Route the device's control lines separately from the supply line.
→ Maintain the greatest possible clearance.

Recommendation: clearance > 10 cm (separate cable
routing)

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 61800-5-1

Compliance with the resistance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device. The protective earth
terminal is located on the housing and provided with a protective earth
symbol and a hole.

4.2.2 Supply connection and fuses

Assignment of supply cable cross-sections and their required fuses (line
protection only, no equipment protection).

Nominal
voltage

Fuse

Automatic
circuit
breaker

Cable
cross-
section

Cable
cross-
section

VDE

UL

VDE

mm²

*AWG

3/PE AC
380-480
VAC

16 A

15 A

C16A

1.5
2.5

16

* AWG = American Wire Gauge

Item no. 50852-5-9970 · ENU · Change 94899 · Approved 2018-03-08 · Page 6 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание M3G084-GF06-42

Страница 1: ...trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules...

Страница 2: ...g items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry while working on rotating...

Страница 3: ...ons and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibit...

Страница 4: ...0 mm 4 Max clearance for screw 12 mm 5 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 6 Tightening torque 3 5 0 5 Nm 7 Groove depth 3 mm 8 Key DIN 6885 A 5 x 5 x 22 Fa Max permissible...

Страница 5: ...e surfaces of the products conform to the generally applicable industrial standard The surface quality may change during the production period This has no effect on strength dimensional stability and...

Страница 6: ...vice malfunctions possible Route the device s control lines separately from the supply line Maintain the greatest possible clearance Recommendation clearance 10 cm separate cable routing NOTE Water in...

Страница 7: ...LA 4 3 Connection in terminal box 4 3 1 Preparing cables for connection Only strip the cable as far as necessary ensuring that the cable gland is sealed and there is no strain on the connections For t...

Страница 8: ...ig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings made for the device by ebm papst Mode PWM control Group address 1 Fan device address 1 Max PWM 100 Min PWM 0 Save se...

Страница 9: ...level KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Use control current sensor value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SELV KL3 4 10 V Voltag...

Страница 10: ...ECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table The status relay drops out and the fault is reported v...

Страница 11: ...o Din1 or by shorting Din1 to GND Impermissible point of operation e g back pressure too high Correct the operating point Let the device cool down To reset the error message switch off the line voltag...

Страница 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 Component disposal The products are...

Отзывы: