Operating instructions

K3G450-AQ06-04

Translation of the original operating instructions

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check whether the data on the type plate agree with the connection
data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Earth wire contact resistance to EN 61800-5-1

Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
connection point available on the device.
The protective earth connection point is located on the housing and has
a protective earth symbol and a bore hole.

4.2.2 Power supply connection, fuse protection

Assignment of conductor cross-sections and the fuse protection required
for them (overload protection only, no device protection).

Nominal
voltage

Safety
fuse

Automatic
circuit
breaker

Wire
cross-
section

Wire
cross-
section

VDE

UL

VDE

mm²

*AWG

3/PE AC
380 - 480
VAC

16 A

15 A

C16A

1.5

16

3/PE AC
380 - 480
VAC

20 A

20 A

C20A

2.5

14

3/PE AC
380 - 480
VAC

25 A

25 A

C25A

4.0

12

3/PE AC
380 - 480
VAC

32 A

30 A

C32A

6.0

10

* AWG = American Wire Gauge

4.2.3 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values lie in a range of typical < 250 mA.

The effective power in this operating state (readiness for operation) is
simultaneously at typical < 5 W.

4.2.4 Residual current operated device

Only universal (type B or B+) RCD protective devices are
permitted. Like frequency inverters, RCD protective devices
cannot provide personal safety while operating the device.
When switching on the power supply of the device, pulsed
charge currents from the capacitors in the integrated EMC filter
can lead to the RCD protective devices triggering without
delay. We recommend residual current devices with a trigger
threshold of 300 mA and delayed triggering (super-resistant,
characteristic K).

4.2.5 Leakage current

For asymmetrical power systems or if a phase fails, the
leakage current can increase to a multiple of the nominal value.

4.2.6 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection in terminal box

4.3.1 Preparing connection lines for the connection

Strip the cable just enough so that the screwed cable gland is tight and
the terminals are relieved of strain. Tightening torque, see chapter 3.1
Product drawing.

Ill. 1: Recommended stripping lengths in mm (inside the terminal box)

4.3.2 Connecting cables with terminals

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Remove the cap from the screwed cable gland.

Remove the cap only in those places where cables are inserted.

Item no. 50561-5-9970 · Revision 69485 · Release 2010-02-05 · Page 7 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G450-AQ06-04

Страница 1: ...assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm papst 1 4 Electrical voltage 1 ...

Страница 2: ...ng on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear...

Страница 3: ...n imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray ...

Страница 4: ... nozzle with bleeder connection for pressure relief k factor 240 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm Item no 50561 5 9970 Revision 69485 Release 2010 02 05 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...om rotor on top on request Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features PFC passive Control input 0 10 VDC PWM Over temperature protected electronics motor Alarm relay Integrated PID controller Input for sensor 0 10 V or 4 20 mA Output for slave 0 10 V RS485 ebmBUS Motor current limit Soft start Line undervoltage phase failure detection Outp...

Страница 6: ...nger be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury from electric shock Use only cables that meet the specified installation requirements for voltage current insulation ...

Страница 7: ... AWG American Wire Gauge 4 2 3 Idle current Because of the EMC filter integrated for compliance with EMC limits interference emission and interference immunity idle currents in the mains cable can be measured even when the motor is at a standstill and the mains voltage is switched on The values lie in a range of typical 250 mA The effective power in this operating state readiness for operation is ...

Страница 8: ...ing No water may penetrate along the cable in the direction of the cable gland When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Ill 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operation mode PWM controlling Group adress 1 Fan device adr...

Страница 9: ...e to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 kΩ only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage output 10 VDC 3 max 10 mA supply voltage for ext devices e g potentiometers SELV KL3 5 20 V Voltage output 20 VDC 25 10 max 50 mA supply voltage for ext devices e g sensors SELV ...

Страница 10: ...ing off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disc...

Страница 11: ...ight clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see ...

Страница 12: ...ry 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual...

Отзывы: