Operating instructions
K3G400-PA27-W4
Translation of the original operating instructions
H = max
. 5
L H x
Assembled FanGrids may not be transported.
There is a risk that the assembly could fall over or be damaged.
If it is not possible to mount the fan combination to the floor, wall and ceiling, the fan combination must be mounted in an auxiliary
construction that is suitably stable.
The construction in which the fans are mounted must have sufficient strength to bear any loads that may occur over the entire service life.
In order to avoid heavy loads due to the composite bending, from a height of four fans and a width of six fans, a consistent, vertical strut
must be installed approximately in the center.
From a width of nine fans, a corresponding number of additional vertical struts must be installed. The struts can be attached both on the
intake side and the outlet side.
The casing between the fans and the wall or ceiling (as a bulkhead) must not be used as a supporting element.
Item no. 56983-5-9970 · ENU · Change 254197 · Approved 2022-05-23 · Page 6 / 20
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com