Operating instructions

K3G400-PA27-W4

Translation of the original operating instructions

4.2.2 Supply connection and fuses

Assignment of supply cable cross-sections and their required fuses (line
protection only, no equipment protection).

Nominal
voltage

Fuse

Automatic
circuit
breaker

Cable
cross-
section

Cable
cross-
section

VDE

UL

VDE

mm²

*AWG

3/PE AC
380-480
VAC

16 A

15 A

C16A

1.5

16

3/PE AC
380-480
VAC

20 A

20 A

C20A

2.5

14

3/PE AC
380-480
VAC

25 A

25 A

C25A

4.0

12

* AWG = American Wire Gauge

4.2.3 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 500 mA.

At the same time, the effective power in this operating state
(operational readiness) is typically < 6 W.

4.2.4 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only AC/DC-sensitive residual current devices
(type B or B+) are permissible. As with variable frequency
drives, residual current devices cannot provide personal safety
while operating the device. When the device power supply is
switched on, pulsed charging currents from the capacitors in the
integrated EMC filter can lead to the instant tripping of residual
current devices. We recommend the use of residual current
circuit breakers (RCCB) with a trip threshold of 300 mA and
delayed tripping (super-resistant, characteristic K).

4.2.5 Leakage current

For asymmetrical power systems or if a phase fails, the
leakage current can increase to a multiple of the nominal value.

4.2.6 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection in terminal box

4.3.1 Preparing cables for connection

Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

Fig. 3: Recommended stripped lengths (inside terminal box)
(1) supply line (2) control and relay line

4.3.2 Terminal connection data

Supply line

min.

max.

Rigid cable cross-
section

0.2 mm²

4 mm²

Flexible cable cross-
section

0.2 mm²

4 mm²

AWG/kcmil cable
cross-section

24

12

Wire-end ferrules with
insulating collar,
in accordance with
DIN 46228-4 for
flexible cable

0.25 mm²

4 mm²

Wire-end ferrules
without insulating
collar,
in accordance with
DIN 46228-1 for
flexible cable

0.25 mm²

4 mm²

NOTE

The cable and cable cross-section must be selected taking into
account the max. starting current of the drive and the type of
cable routing (see Chapter 4.2.2 Supply connection and fuses)

Item no. 56983-5-9970 · ENU · Change 254197 · Approved 2022-05-23 · Page 10 / 20

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G400-PA27-W4

Страница 1: ...test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device i...

Страница 4: ...Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k...

Страница 5: ...fans Use M8 or 8 mm diameter screws and if necessary screw anchors of sufficient size and strength that the fan assembly cannot come loose even under heavy load Maximum height 5 FanGrid fans vertical...

Страница 6: ...the entire service life In order to avoid heavy loads due to the composite bending from a height of four fans and a width of six fans a consistent vertical strut must be installed approximately in the...

Страница 7: ...duction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019...

Страница 8: ...for professionally used equipment with a total rated power greater than 1 kW If several devices are connected in parallel on the supply side so that the line current of the arrangement is in the range...

Страница 9: ...ons CAUTION Voltage The fan is a built in component and has no disconnecting switch Only connect the fan to circuits that can be switched off with an all pole disconnection switch When working on the...

Страница 10: ...esidual current circuit breakers RCCB with a trip threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 5 Leakage current For asymmetrical power systems or if a phase fails the...

Страница 11: ...cable diameter the seals included in the terminal box must be inserted into the cable gland if necessary Route the cable s not included in the scope of delivery into the terminal box Ensure separate r...

Страница 12: ...ble a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Страница 13: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Страница 14: ...159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active...

Страница 15: ...operating instructions 4 7 Equivalent circuit diagrams Item no 56983 5 9970 ENU Change 254197 Approved 2022 05 23 Page 15 20 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Страница 16: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 17: ...automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the device to...

Страница 18: ...nsors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is t...

Страница 19: ...on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecolog...

Страница 20: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 56983 5 9970 ENU Change 254197 Approved 2022 05 23 Page 20 20 ebm papst Mulfinge...

Отзывы: