Operating instructions

K3G355-AY43-22

Translation of the original operating instructions

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection in terminal box

4.3.1 Preparing cables for connection

Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

Fig. 2: Recommended stripped lengths in mm (inside terminal box)
Legend: CL = control lines

4.3.2 Connecting wires to terminals

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Remove the cap from the cable gland.

Only remove caps where cables are fed in.

;

Equip the cable glands with the seals provided in the terminal box.

;

Route the wire(s) (not included in scope of delivery) into the terminal
box.

;

First connect the "PE" (protective earth).

;

Connect the wires to the corresponding terminals.

Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.

Fig. 3: Connecting wires to terminals

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

4.4 Factory settings

Factory settings made for the device by ebm-papst.

Mode parameter set 1

PWM control

Mode parameter set 2

PWM control

Fan/device address

1

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

Yes

Set value requirement

Analog (linear)

Direction of action
parameter set 1

Positive (heating)

Direction of action
parameter set 2

Positive (heating)

Item no. 51309-5-9970 · ENU · Change 212946 · Approved 2020-07-14 · Page 8 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-AY43-22

Страница 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...he operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposit...

Страница 4: ...max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Installation position Shaft horizontal only install support struts vertically as illustrated or rotor at bottom rotor on top on re...

Страница 5: ...rP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 23 5 kg Size 355 mm Motor size 112 Rotor surface Painted black Electronics...

Страница 6: ...g Carefully remove the device from the packaging by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Ri...

Страница 7: ...ent level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross section equal to or greater than that o...

Страница 8: ...inal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 3 Connecting wires to te...

Страница 9: ...ly usable as alternative to input Ain1 I SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for external devices e g pot SELV KL3 6 Ain1 I Analog input 1 set...

Страница 10: ...only usable as alternative to input Ain2 I SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for external devices e g sensors SELV Alternatively 24 VD...

Страница 11: ...ossibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with...

Страница 12: ...am Motor electronics overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again The...

Страница 13: ...n measurement Recommended every 6 months Clean impeller or replace device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst opera...

Страница 14: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51309 5 9970 ENU Change 212946 Approved 2020 07...

Отзывы: