3.2 Nominal data

Motor

M3G112-GA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

2450

Power consumption / W

1400

Current draw / A

6.0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

50

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

63.8

53

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

72.8

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

K3G355-AY43-22

09 Power consumption P

ed

/ kW

1.4

09 Air flow q

v

/ m³/h

3755

09 Pressure increase total p

sf

/

Pa

794

10 Speed (rpm) n / min

-1

2380

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

23.5 kg

Size

355 mm

Motor size

112

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Impeller material

Sheet aluminum

Support plate material

Sheet steel, galvanized

Support bracket
material

Steel, painted black

Inlet nozzle material

Sheet steel, galvanized

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

See product drawing

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Tach output
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
- External release input
- Alarm relay
- Integrated PID controller
- Power limit
- Motor current limitation
- PFC, active
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

EAC; UL 1004-7 + 60730-1

Item no. 51309-5-9970 · ENU · Change 212946 · Approved 2020-07-14 · Page 5 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-AY43-22

Страница 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...he operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposit...

Страница 4: ...max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Installation position Shaft horizontal only install support struts vertically as illustrated or rotor at bottom rotor on top on re...

Страница 5: ...rP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 23 5 kg Size 355 mm Motor size 112 Rotor surface Painted black Electronics...

Страница 6: ...g Carefully remove the device from the packaging by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Ri...

Страница 7: ...ent level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross section equal to or greater than that o...

Страница 8: ...inal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Fig 3 Connecting wires to te...

Страница 9: ...ly usable as alternative to input Ain1 I SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for external devices e g pot SELV KL3 6 Ain1 I Analog input 1 set...

Страница 10: ...only usable as alternative to input Ain2 I SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for external devices e g sensors SELV Alternatively 24 VD...

Страница 11: ...ossibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with...

Страница 12: ...am Motor electronics overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again The...

Страница 13: ...n measurement Recommended every 6 months Clean impeller or replace device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst opera...