Operating instructions

K3G310-RR18-R8

Translation of the original operating instructions

No.

Conn.

Designation

Color

Function/assignment

3

3

GND

-

Reference ground for control interface, SELV

3

4

0-10 V / PWM

-

Analog input (set value) SELV, 0-10 V, Ri = 100 kΩ, adjustable curve

3

5

+10 V

-

Fixed voltage output 10 VDC, SELV, +10 V +/-3%, max. 10 mA, short-circuit-proof, power
supply for external devices (e.g. potentiometers)

3

6

RES

-

Reserve

3

7

COM*

-

Alarm COM*

3

8

NC*

-

NC* KL3 UMAX 24 V

3

9

Schirm

-

Shield

4

1

RSA

-

RS485 interface for MODBUS, RSA; SELV

4

2

RSB

-

RS485 interface for MODBUS, RSB; SELV

4

7

LED R

-

External LED Red

4

8

LED G

-

External LED Green

4

9

Schirm

-

Shield

Item no. 54490-5-9970 · ENU · Change 200267 · Approved 2019-02-14 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G310-RR18-R8

Страница 1: ...aff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safet...

Страница 2: ...be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rota...

Страница 3: ...Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 5 Transport and storage conditions and Chapter 3...

Страница 4: ...3 L 3 8 pole socket housing tyco 100616 2 4 8 pole socket housing tyco 100616 2 5 8 pole socket housing tyco 100616 2 6 Switch ARCOLECTRIC SWITCHES P L C no H8550VBACF As delivered condition end cust...

Страница 5: ...ction Touch current according to IEC 60990 measuring circuit Fig 4 TN system 3 5 mA Electrical hookup Plug Motor protection Thermal overload protector TOP internally connected with cable Variable Prot...

Страница 6: ...ng purposes Position the round slings as shown in the hoisting diagram below Make sure that the struts of the support bracket on the left and right of the motor are vertical Transport the centrifugal...

Страница 7: ...in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current circuit breaker RCCB If the use of a residual current dev...

Страница 8: ...terface SELV 2 4 0 10 V PWM Analog input set value SELV 0 10 V Ri 100 k adjustable curve 2 5 10 V Fixed voltage output 10 VDC SELV 10 V 3 max 10 mA short circuit proof power supply for external device...

Страница 9: ...short circuit proof power supply for external devices e g potentiometers 3 6 RES Reserve 3 7 COM Alarm COM 3 8 NC NC KL3 UMAX 24 V 3 9 Schirm Shield 4 1 RSA RS485 interface for MODBUS RSA SELV 4 2 RSB...

Страница 10: ...input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in c...

Страница 11: ...ularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion...

Страница 12: ...specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the...

Отзывы: