Operating instructions

G2D146-BF04-24

Translation of the original operating instructions

4.3.3 Cable routing

No water may penetrate along the cable in the direction of the cable gland.
When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 2: Cable routing for fans installed upright.

4.3.4 Motor protection

WARNING
Device without overheating protection

The device is delivered without any automatically functioning
overheating protection. The device can become hot and burn.
→ For the version without TOP, install an additional, suitable

motor protection switch.

Item no. 13912-5-9970 · Revision 82464 · Release 2014-04-07 · Page 7 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G2D146-BF04-24

Страница 1: ...echnical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rule...

Страница 2: ...lled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installat...

Страница 3: ...ing the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operat...

Страница 4: ...measures have the unit mm 1 Tightening torque 2 0 0 3 Nm 2 Cable diameter min 6 mm max 9 mm tightening torque 1 3 0 2 Nm Item no 13912 5 9970 Revision 82464 Release 2014 04 07 Page 4 10 ebm papst Mul...

Страница 5: ...idity class F1 1 Mounting position Any Condensate discharge holes None Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Electrical lea...

Страница 6: ...h must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG26 0 13 mm Earth...

Страница 7: ...Cable routing for fans installed upright 4 3 4 Motor protection WARNING Device without overheating protection The device is delivered without any automatically functioning overheating protection The d...

Страница 8: ...phase motor Y Star connection Delta connection L1 U1 blue L2 V1 black L3 W1 brown U2 white V2 green W2 yellow Item no 13912 5 9970 Revision 82464 Release 2014 04 07 Page 8 10 ebm papst Mulfingen GmbH...

Страница 9: ...the supply line When disconnecting be sure to disconnect the earth wire connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the dev...

Страница 10: ...l inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting...