background image

Operating instructions

G1G126-AA49-71

Translation of the original operating instructions

You can control the blower either via the 0-10 VDC input or the
PWM input. Attention: The inputs cannot be used simultaneously.

3.2 Nominal data

Motor

M1G055-BD

Phase

1~

Nominal voltage / VAC

230

Frequency / Hz

50/60

Method of obtaining
data

fa

Speed (rpm) / min

-1

5000

Power consumption / W

75

Current draw / A

-

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

70

Min. temp. of flow
medium / °C

-25

Max. temp. of flow
medium / °C

80

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

1.5 kg

Size

126 mm

Motor size

55

Rotor surface

Thick-film passivated

Cover material

PP plastic

Impeller material

PA plastic

Housing material

Die-cast aluminum

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP20

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H0 - dry environment

Installation position

Any

Condensation
drainage holes

None

Mode

S1

Premixing

Not suitable for premixing.

Motor bearing

Ball bearing

Technical features

- Tach output
- Motor current limitation
- PWM control input

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Plug

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

CE

Approval

EAC; CCC

Comment

Complete unit must be tested for required
approvals.

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

For screw clearance, see Chapter 3.1 Product drawing

Strength class of
screws

8.8

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 51256-5-9970 · ENU · Change 202174 · Approved 2018-12-27 · Page 6 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G1G126-AA49-71

Страница 1: ...ined and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1...

Страница 2: ...electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Danger of injury from open blower Escaping...

Страница 3: ...perature range see Chapter 3 5 Transport and storage conditions and Chapter 3 2 Nominal data Using the device only in stationary systems Installing the device in an integrated system for conveying air...

Страница 4: ...r life support function Conveying solids in the flow medium Painting the device Connections e g screws coming loose during operation Item no 51256 5 9970 ENU Change 202174 Approved 2018 12 27 Page 4 1...

Страница 5: ...very Tyco no 350 766 1 socket Tyco no 926 884 1 2 1 L 2 2 N 2 3 PE 3 5 pole header mating connector not included in scope of delivery Molex no 39 01 4050 socket Molex no 39 00 0059 3 1 3 2 Speed monit...

Страница 6: ...andards CE Approval EAC CCC Comment Complete unit must be tested for required approvals With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one m...

Страница 7: ...t not be strained on fastening 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the protective earth DANGER Faulty insulation Risk of...

Страница 8: ...he integrated EMC filter can lead to the instant tripping of residual current devices We recommend the use of residual current circuit breakers RCCB with a trip threshold of 300 mA and delayed trippin...

Страница 9: ...ting instructions 4 4 Connection diagram Drawing preliminary Item no 51256 5 9970 ENU Change 202174 Approved 2018 12 27 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49...

Страница 10: ...tching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power suppl...

Страница 11: ...pst operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development...

Страница 12: ...r internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 512...

Отзывы: