background image

Operating instructions

D2E146-AP47-02

Translation of the original operating instructions

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

If you have any other problems, contact ebm-papst.

5.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

5.2 Safety test

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean or
replace impeller

Check the ball
bearings to
ensure they
are quiet, can
move easily
and are free of
play

Manual check
by turning the
rotor in shut-off
state

At least every
6 months

Replace
device in case
of noise,
difficulty of
movement or
clearance of
the bearings

Item no. 10542-5-9970 · Revision 68158 · Release 2011-03-30 · Page 9 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание D2E146-AP47-02

Страница 1: ...em Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or...

Страница 2: ... could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect...

Страница 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Страница 4: ...A 3 1 Product drawing All measures have the unit mm 1 Connection line PVC 4x brass lead tips crimped Item no 10542 5 9970 Revision 68158 Release 2011 03 30 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...ed Housing material Sheet steel hot dip galvanised Direction of rotation Counter clockwise seen on rotor Type of protection IP 44 Insulation class B Humidity class F0 Mounting position Any Condensate discharge holes None Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Motor protection Thermal overload protector TOP wired internally...

Страница 6: ...ected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data and the data of the operating capacitor Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current ...

Страница 7: ...structions 4 4 Connection screen U1 blue Z brown U2 black PE green yellow Item no 10542 5 9970 Revision 68158 Release 2011 03 30 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 8: ...d off Electric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury Keep out of the danger zone of the device When working on the device switch off the mains supply voltage and secure the latter from being switched on again Wait until the device stops If the d...

Страница 9: ...Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every ...

Отзывы: