Operating and Maintenance Instructions
210-OMI14229-Iss8.1
CN1116 Full OMI
Page 39 of 47
© ebm-papst UK Ltd 2021
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
Appendix G
–
Example of Modbus Relay Operation
Initial Configuration Steps
•
BMS Network has slave addresses 1 and 2 available i.e., not taken by any other device
•
Both MDCs have successfully addressed all their respective fans
•
Both MDCs have changed their operating mode to “Monitor & Control” (the control mode is not
important)
o
See
Operation Mode - Monitor & Control
o
This step is purely taken to set all fans to “Modbus” speed control
as opposed to their factory
settings of
“Analogue 0
-
10V” speed control
•
MDC1 Modbus Slave address is kept a
t its factory setting value of “1”
•
MDC2 Modbus Slave address has been changed
to “2”
, see
•
Both MDCs have changed their operating mode to “Modbus Relay”, see
Example of setting the speed of Fan 4 (at Fan Array 1) to 100%:
BMS writes
“
6553
5”
to Holding Register
Address 801 (hex) of MDC1 (Modbus Slave Address 1). This is Holding Register D001 of Fan 4 of MDC1.
Example of reading the Motor Status Register of Fan 3 (at Fan Array 2):
BMS reads input register address
40B (hex) of MDC 2 (Modbus Slave Address 2). This is Input Register D011 of Fan 3 of MDC2.
NOTE 1:
Do not to read/write more than 9 consecutive “
retrieved
from fan” registers at a time,
otherwise a Modbus Exception Response will occur.
NOTE 2: The controller will respond to the BMS after the communication with the fan has completed.
A Modbus Exception Response will be returned to the BMS if the read/write to the fan has failed or the
fan has no comms.
220Ω
220Ω