ebm-papst A4E300-AP26-70 Скачать руководство пользователя страница 9

Operating instructions

A4E300-AP26-70

Translation of the original operating instructions

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

If you have any other problems, contact ebm-papst.

5.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

5.2 Safety test

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Condensate
discharge
holes for
clogging, as
necessary

Visual inspection At least every

6 months

Open bore holes

Weld seams
for crack
formation

Visual inspection At least every

6 months

Replace unit

Check the ball
bearings to
ensure they
are quiet, can
move easily
and are free of
play

Manual check
by turning the
rotor in shut-off
state

At least every
6 months

Replace
device in case
of noise,
difficulty of
movement or
clearance of
the bearings

Item no.: 10743-5-9970 · Revision: --- · Print-out: 2012-02-16 · Y. Uhlmann (VM-TDO) · Page 9 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A4E300-AP26-70

Страница 1: ...ystem Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic saf...

Страница 2: ...ome entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depend...

Страница 3: ...following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly co...

Страница 4: ...measures have the unit mm 1 Direction of air flow A 2 Connection line PVC 4x brass lead tips crimped 3 Depth of screw max 5 mm Item no 10743 5 9970 Revision Print out 2012 02 16 Y Uhlmann VM TDO Page...

Страница 5: ...harge holes Rotor side Operation mode S1 Motor bearing Ball bearing Leakage current 0 75 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection class I if p...

Страница 6: ...ed in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the...

Страница 7: ...ions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 10743 5 9970 Revision Print out 2012 02 16 Y Uhlmann VM TDO Page 7 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Страница 8: ...lectric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury...

Страница 9: ...device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of p...

Отзывы: