ebm-papst A4E300-AP26-70 Скачать руководство пользователя страница 5

Operating instructions

A4E300-AP26-70

Translation of the original operating instructions

3.2 Nominal data

Motor

M4E068-CF

Phase

1~

1~

Nominal voltage in VAC

230

230

Frequency in Hz

50

60

Type of data definition

fa

fa

Valid for approval /
standard

CE

CE

Speed in min

-1

1400

1630

Power input in W

68

92

Current draw in A

0.3

0.41

Motor capacitor in µF

2

2

Capacitor voltage in VDB

400

400

Max. back pressure in Pa

80

70

Max. ambient
temperature in °C

60

45

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Technical description

Mass

2 kg

Size

300 mm

Surface of rotor

Coated in black

Material of blades

Sheet steel, coated in black

Number of blades

5

Direction of air flow

"A"

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 44

Insulation class

"B"

Humidity class

F1-2

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Leakage current

< 0.75 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1; CE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Graphic rendition of products

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no.: 10743-5-9970 · Revision: --- · Print-out: 2012-02-16 · Y. Uhlmann (VM-TDO) · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A4E300-AP26-70

Страница 1: ...ystem Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic saf...

Страница 2: ...ome entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depend...

Страница 3: ...following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly co...

Страница 4: ...measures have the unit mm 1 Direction of air flow A 2 Connection line PVC 4x brass lead tips crimped 3 Depth of screw max 5 mm Item no 10743 5 9970 Revision Print out 2012 02 16 Y Uhlmann VM TDO Page...

Страница 5: ...harge holes Rotor side Operation mode S1 Motor bearing Ball bearing Leakage current 0 75 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection class I if p...

Страница 6: ...ed in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the...

Страница 7: ...ions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 10743 5 9970 Revision Print out 2012 02 16 Y Uhlmann VM TDO Page 7 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Страница 8: ...lectric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury...

Страница 9: ...device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of p...

Отзывы: