Operating instructions

A3G910-AO84-21

Translation of the original operating instructions

4.5 Connection diagram

Line

No.

Signal

Colour

Function / assignment

1

1,2

PE

green/yellow Protective earth

1

3

N

blue

Supply voltage, neutral conductor, 50/60 Hz

1

4

L

black

Supply voltage, phase, 50/60 Hz

1

5

COM

white 1

Floating status message contact, normally closed for error (2 A, max. 250 VAC, min. 10 mA, AC1)

1

6

NC

white 2

Floating status message contact, normally closed for error

2

8

0-10 V

yellow

Control input, set value 0-10 VDC, impedance 100 kΩ, SELV

2

11

10 VDC

red

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for external devices (e.g.
potentiometer), SELV

2

12

GND

blue

Reference mass for control interface, SELV

Item no.: 50437-5-9970 · Revision: 73097 · Print-out: 2012-04-11 · Y. Uhlmann (VM-TDO) · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G910-AO84-21

Страница 1: ...ack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is...

Страница 2: ...the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or bro...

Страница 3: ...s is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving funct...

Страница 4: ...ection of air flow V 2 Depth of screw 12 16 mm 3 Connection line AWG18 5 x crimped core end sleeves 4 Connection line AWG22 3 x crimped core end sleeves Item no 50437 5 9970 Revision 73097 Print out 2...

Страница 5: ...t Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features PFC active Output 10 VDC max 10 mA Alarm relay Control input 0 10 VDC PWM Over temperature prote...

Страница 6: ...ther the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for curr...

Страница 7: ...routed in the form of a loop water trap The bushing must not be kinked during this process Fans installed in upright position Ill 2 Cable routing for fans installed in upright position The cables must...

Страница 8: ...2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status message contact normally closed for error 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 k SELV 2 11 10 VDC red Voltage o...

Страница 9: ...ion on and off via power supply Switching off the device for maintenance work Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Dis...

Страница 10: ...esponded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool do...

Страница 11: ...s Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace unit Check the ball bearings to ensure they are quiet can move easily and are free of play Manual che...