ebm-papst A3G450-BL03-H6 Скачать руководство пользователя страница 7

Operating instructions

A3G450-BL03-H6

Translation of the original operating instructions

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

;

Note the following when routing the cables:
For permanently installed lines, the bending radius must be at least
four times the outside diameter of the cable.
For movable lines, the bending radius must be at least 15 times the
outside diameter of the cable.

Protective earth contact resistance according to EN 61800-5-1

Compliance with the resistance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device. The protective earth
terminal is located on the housing and provided with a protective earth
symbol and a hole.
After connecting protective earth, ensure sufficient additional corrosion
protection.

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only AC/DC-sensitive residual current devices
(type B or B+) are permissible. As with variable frequency
drives, residual current devices cannot provide personal safety
while operating the device. When the device power supply is
switched on, pulsed charging currents from the capacitors in the
integrated EMC filter can lead to the instant tripping of residual
current devices. We recommend the use of residual current
circuit breakers (RCCB) with a trip threshold of 300 mA and
delayed tripping (super-resistant, characteristic K).

4.2.4 Basic insulation of the alarm relay

As the alarm relay only has basic insulation (for TN/TT
systems) or functional insulation (for phase-conductor-grounded
networks) with respect to the supply voltage, and not double
insulation like the rest of the interface, corresponding precautions
must be taken for industrial applications (EN 61800-5-1).
→ The voltage switched by the alarm relay (e.g. 24 VDC)

must then have no electrical connection to the 10 V output, 0-
10 V control input and GND (electrically isolated interface).

4.2.5 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection via terminal strip

4.3.1 Connecting wires to terminals

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Insert the wires into the terminals, see
Chapter 4.5 Connection diagram.

4.4 Factory settings

Factory settings made for the device by ebm-papst.

Mode parameter set 1

Speed control

Mode parameter set 2

Speed control

Fan/device address

1

Max. PWM / %

100

Min. PWM / %

5

Save set value to
EEPROM

No

Item no. 53897-5-9970 · ENU · Change 211129 · Approved 2020-07-14 · Page 7 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G450-BL03-H6

Страница 1: ...cialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated wi...

Страница 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Страница 3: ...ctions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation...

Страница 4: ...e of seal provided Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 4 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use must be made of seal provided Cable diameter min...

Страница 5: ...otor impeller combination in a standardized measurement setup 3 4 Technical description Weight 4 8 kg Size 450 mm Motor size 84 Rotor surface Painted black Electronics housing material Die cast alumin...

Страница 6: ...only the blades near the hub Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface M...

Страница 7: ...rotective earth ensure sufficient additional corrosion protection 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to inte...

Страница 8: ...ear Direction of action parameter set 1 Positive heating Direction of action parameter set 2 Positive heating Item no 53897 5 9970 ENU Change 211129 Approved 2020 07 14 Page 8 12 ebm papst Mulfingen G...

Страница 9: ...act common connection contact rating 250 VAC 2 A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 8 GND Reference ground for control interface SELV 9 R...

Страница 10: ...ound connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety fea...

Страница 11: ...oaking installation in the barn they have to be manually soaked separately using a hosepipe or knapsack sprayer for example Instructions for cleaning Fig 1 Cleaning of the fan with a high pressure cle...

Страница 12: ...to be heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitab...

Отзывы: