Operating instructions

W3G800-LU21-03

Translation of the original operating instructions

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Broken motor winding Replace device
Inadequate cooling

Improve cooling.
Allow the device to
cool down.

Ambient temperature
too high

Reduce the ambient
temperature. Allow
the device to cool
down.

Impermissible
operating point (e.g.
back pressure too
high)

Correct the operating
point. Allow the
device to cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Warning/status codes

The LED on the electronics housing shows the motor status with various
colors and flash codes. The flash codes have a frequency of 2 Hz.
Each flash code is followed by a pause lasting 3 seconds. The following
colors are used: Green: no warning or fault. Orange: There is a warning.
No user intervention is required for warnings. Red: There is at least one
error. See the following table. If there are multiple simultaneous errors,
their associated flash codes are displayed in succession. If there are
simultaneous warnings and errors, only the errors are displayed.

6.1.1 Warning codes

Number of pulses

Motor status - LED
orange

Message at status
relay

1

Current limitation in
action

2

Line impedance too
high (DC-link voltage
unstable)

3

Power limiter in action

4

Output stage
temperature high

5

Motor temperature high

6

Temperature inside
electronics high

7

DC-link voltage low

8

Braking mode: set in
case of external drive
in opposite direction
at high speed for
lengthy period

Yes

9

Calibration of rotor
position sensor in
progress

10

Actual speed is lower
than run monitoring
speed limit

Yes

11

Open circuit at analog
input or PWM input
for the set value

Yes

13

DC-link voltage high

15

Line voltage high

16

Shake-loose function
activated

6.1.2 Status codes

Manual reset by "Switch off line voltage - wait briefly - switch line
voltage back on" or, if provided,
via the "Fan enable/disable" input

Number of
pulses

Motor status -
LED red

Possible cause Possible

remedy

1

Phase failure or
line undervoltage

Missing phase
Poor power
supply quality

Check line
voltage

3

Output stage
overheating

Electronics
housing
contaminated

Provide better
cooling.
Manual reset
required

4

Communication
error between
master
controller and
slave controller

External
supply applied
via Vout for
setting
parameters.
Internal error

Switch off line
voltage
- wait -
switch back on

6

Motor
overheating

Ambient
temperature too
high
Impermissible
operating point

Reduce
ambient
temperature
Correct
operating point.
Manual reset
required

7

Hall sensor error Internal error

Switch off line
voltage
- wait -
switch back on

8

Motor blocked

Mechanical
blockage

Switch off
- check safe
isolation from
supply -
check
freedom of
movement of
rotor

Item no. 56111-5-9970 · ENU · Change 212910 · Approved 2020-10-28 · Page 14 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G800-LU21-03

Страница 1: ...to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the workplace clean and tidy Untidiness in the work a...

Страница 2: ... g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body par...

Страница 3: ...n stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device...

Страница 4: ... designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Tightening torque 3 0 3 Nm 5 Attachment holes for FlowGrid 80000 2 2957 not included in scope of delivery Item no 56111 5 9970 ENU Change 212910 Approved 2020 10 28 Page 4 16 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fa...

Страница 5: ... rings The dimensions must be requested from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight...

Страница 6: ...d is greater than or equal to 250 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP...

Страница 7: ...e with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided wit...

Страница 8: ...section must be selected taking into account the max starting current of the drive and the type of cable routing see Chapter 4 2 2 Supply connection and fuses Control and relay cables min max Rigid cable cross section 0 2 mm 1 5 mm Flexible cable cross section 0 2 mm 1 5 mm AWG kcmil cable cross section 24 16 Wire end ferrules with insulating collar in accordance with DIN 46228 4 for flexible cabl...

Страница 9: ...he sealing surfaces are clean Screw in the four screws for tightening torque see Chapter 3 1 Product drawing 4 3 4 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable gla...

Страница 10: ...teristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve parameterizable see output characteristic curve P3 OUT SELV CON2 Vout Voltage output 3 3 24 VDC 5 Pmax 800 mW voltage parameterizable Factory setting 10 VDC short circuit proof supply for external devices...

Страница 11: ...D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active pin open or applied voltage 1 5VDC active applied voltage 3 5 50VDC SELV D15A 0 Din3 active low digital input not active pin open or applied voltage 3 5 50VDC active app...

Страница 12: ... operating instructions 4 7 Equivalent circuit diagrams Item no 56111 5 9970 ENU Change 212910 Approved 2020 10 28 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 13: ... supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the...

Страница 14: ...tus LED orange Message at status relay 1 Current limitation in action 2 Line impedance too high DC link voltage unstable 3 Power limiter in action 4 Output stage temperature high 5 Motor temperature high 6 Temperature inside electronics high 7 DC link voltage low 8 Braking mode set in case of external drive in opposite direction at high speed for lengthy period Yes 9 Calibration of rotor position ...

Страница 15: ...als to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of the AC voltage required by the standard What to check How t...

Страница 16: ...inum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electric...

Отзывы: