Operating instructions

R3G450-PA31-03

Translation of the original operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

If the device is out of use for over four months, we recommend
switching it on for at least three hours at full speed to allow any
condensation to evaporate and to move the bearings.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Broken motor winding Replace device
Inadequate cooling

Improve cooling.
Allow the device to
cool down.

Ambient temperature
too high

Reduce the ambient
temperature. Allow
the device to cool
down.

Impermissible
operating point (e.g.
back pressure too
high)

Correct the operating
point. Allow the
device to cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Warning/status codes

The LED on the electronics housing shows the motor status with various
colors and flash codes. The flash codes have a frequency of 2 Hz.
Each flash code is followed by a pause lasting 3 seconds. The following
colors are used: Green: no warning or fault. Orange: There is a warning.
No user intervention is required for warnings. Red: There is at least one
error. See the following table. If there are multiple simultaneous errors,
their associated flash codes are displayed in succession. If there are
simultaneous warnings and errors, only the errors are displayed.

Number of
pulses

Motor
status -
LED red

Manual
reset
required

Possible
cause

Possible
remedy

1

Phase
failure or
line
undervoltage

no

Missing
phase
Poor grid
quality

Check line
voltage

3

Output
stage
overheating.

yes

Dirty
electronics
housing.

Improve
cooling.

4

Communication
error
between
master
controller
and slave
controller

no

External
supply
applied via
Vout for
setting
parameters.
Internal
error.

Switch off
line voltage
- wait
- switch
back on.

6

Motor
overheating

yes

Ambient
temperature
too high.
Impermissible
operating
point.

Lower the
ambient
temperature.
Correct
the
operating
point.

7

Hall sensor
fault

yes

Internal error Switch off

line voltage
- wait
- switch
back on.

8

Motor
blocked

no

Mechanical
blockage

Switch off
- Verify
isolation
from supply
- Check
rotor
freedom of
movement.

9

Speed limit
exceeded

no

-

-

Item no. 55777-5-9970 · ENU · Change 200980 · Approved 2018-12-05 · Page 14 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G450-PA31-03

Страница 1: ...rry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following ins...

Страница 2: ...ling the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or th...

Страница 3: ...g the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt depo...

Страница 4: ...essure tap k factor 240 not included in scope of delivery 2 Max clearance for screw 20 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 0 3 Nm 4 Tightening torque 1 5 0 2 Nm Item no 55777 5...

Страница 5: ...n mm inlet ring 45075 2 4013 with pressure tap k factor 240 not included in scope of delivery Item no 55777 5 9970 ENU Change 200980 Approved 2018 12 05 Page 5 16 ebm papst Mulfingen GmbH Co KG Bachm...

Страница 6: ...er combination in a standardized measurement setup 3 4 Technical description Weight 21 3 kg Size 450 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast aluminum Impell...

Страница 7: ...e responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection poi...

Страница 8: ...earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Supply connection and fuses Assignment of sup...

Страница 9: ...re ends fan out Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into t...

Страница 10: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Страница 11: ...put Ri 100K characteristic curve parameterizable fPWM 1k 10KHz SELV D159 2 Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active p...

Страница 12: ...operating instructions 4 7 Equivalent circuit diagrams Item no 55777 5 9970 ENU Change 200980 Approved 2018 12 05 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Страница 13: ...ce from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant freq...

Страница 14: ...wn Ambient temperature too high Reduce the ambient temperature Allow the device to cool down Impermissible operating point e g back pressure too high Correct the operating point Allow the device to co...

Страница 15: ...of cables for damage Visual inspection At least every 6 months Replace cables Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean impeller or replace device...

Страница 16: ...lating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magn...

Отзывы: