background image

 

EVMS/EVMSL 

 

- 4 - 

 

Caution

 

Do not operate the pump with 50 Hz specifications at 60 Hz. 
Doing so will overload the pump, causing the motor to burn. 

 

Do not operate the pump with 60 Hz specifications at 50 Hz. 
Doing so will cause the pump to perform poorly. 

 

If  you  have  purchased  a  standard  pump,  refer  to  the  standard 
specifications shown below. The optional specifications indicate 
changes  made  to  some  pumps  to  meet  the  needs  of  some 
customers.  Be  sure  not  to  operate  your  pump  outside  of  the 
ranges shown in the applicable specifications. 

 

The equipment cannot be used for food-related fluid transport. 

 

In important facilities (computer cooling facilities, freezer cooling 
facilities, etc.) always prepare a spare pump for pump failures. 

 

There  will  be  entrainment  of  cutting  lubricant  contained  in  the 
piping system, as well as rubber mould releasing agent, foreign 
material, etc. Carry out flushing sufficient for the equipment, and 
confirm before use.   

 

Make sure that the floor surface where the pump is installed has 
been  waterproofed  and  treated  for  waste  water.  If  it  has  not, 
severe damage could be caused should leakage occur. 

 

Make  sure  that  any  one  of  three  terminals  of  the  three-phase 
motor is not loose or disconnected. Running the motor with only 
two terminals connected could a phase interruption, burning out 
the motor. 

 

Pump  failures  are  possible  when  operated  with  less  flow  rate 
than appropriate for the pump size (nominal inlet bore diameter 
in mm) (e.g. 50 L/min for size of 50 mm). When operation may 
occur  with  a  small  flow  rate,  install  relief  pipes,  etc.  to  ensure 
operation at or above this flow. 

 

If  air  is  entrained  during  pumping  and  is  not  discharged,  the 
bearings  and  shaft  seals  may  be  damaged,  and  pumping  may 
be impossible. Avoid this situation. 

 

Do  not  touch  the  pump  when  the  liquid  handled  is  hot  water. 
Burns may result from high temperatures. 

 

D

o  not  touch  the  motor.  The  motor’s  surfaces  will  be  hot,  and 

you could get burned if you touch them. 

 

Do not cover the  motor with a blanket or cloth. Doing so could 
over heat the motor, setting a fire. 

 

To  prevent  an  accident  if  the  pump  stops  running  or  an 
abnormality  occurs,  immediately  turn  off  the  power  switch. 
Contact the shop from where you ordered the pump, or EBARA 
to perform an inspection and maintenance on the pump. 

 

When the pump is out of use for prolonged periods such as the 
wintertime,  water  inside  the  pump  could  freeze,  causing 
damage  to  the  pump.  Accordingly,  in  such  situations,  either 
drain  all  water  from  the  pump  or  provide  thermal  insulation  to 
prevent the water from freezing. 

 

Never disassemble the motor. When disassembly is necessary, 
contact EBARA. 

 

Содержание 25EVMS106.75

Страница 1: ...opies of this manual to the customer s pump operation maintenance and inspection personnel Keep this manual in a safe place where it can be consulted at any time To installation personnel Be sure to i...

Страница 2: ...tions that they give without fail Warning grade Meaning Warning Potentially hazardous situation Failure to follow the instructions could result in death or serious injury Caution Failure to follow the...

Страница 3: ...the discharge valve left closed The pressure within the pump will rise and the casing or plugs may be damaged Do not touch the rotating parts such as the spindle shaft couplings V pulleys etc while t...

Страница 4: ...ected Running the motor with only two terminals connected could a phase interruption burning out the motor Pump failures are possible when operated with less flow rate than appropriate for the pump si...

Страница 5: ...and that bolts and nuts have not become loose Nameplate The pump s basic specifications are inscribed on the nameplate Check the nameplate to ensure that the equipment is as ordered Caution Do not op...

Страница 6: ...orm of optional specifications on request of the customer Do not use the equipment beyond the scope of the specifications The equipment cannot be used for food related fluid transport In facilities wi...

Страница 7: ...S329A Wear ling Model EVMS PPS SUS304 Model EVMSL PPS SUS316 Motor 4 5 Phase pole 3 phase 2 pole Voltage 50Hz 200V 60Hz 200 220 230V Type Totally enclosed fan cooling type outdoor Efficiency IE3 Premi...

Страница 8: ...l seal SiC SiC type Liquid temperature 0 90 Purified water type Liquid temperature 25 5 Different motor Different voltage Special different voltage Terminal box position change every 90 Tropical treat...

Страница 9: ...2EVMS L 35 55 1 09 11 1 32EVMS L 45 75 0 99 10 1 32EVMS L 551 1 0 88 9 32EVMS L 751 5 0 69 7 32EVMS L 1152 2 0 30 3 1 32EVMS L 1553 0 0 99 10 1 32EVMS L 2054 0 0 51 5 2 32EVMS L 2755 5 0 08 0 8 40 40E...

Страница 10: ...75 26 75 361 1 461 5 662 2 863 0 1164 0 1565 5 1967 5 1 09 11 1 32EVMS L 361 1 0 95 9 7 32EVMS L 461 5 0 81 8 3 32EVMS L 662 2 0 53 5 4 32EVMS L 863 0 0 25 2 5 32EVMS L 1164 0 0 92 9 4 32EVMS L 1565...

Страница 11: ...hould be 40 or below 5 Select a place that is convenient for pump maintenance 6 Take measures such as enclosing the pump to keep unqualified personnel away from the equipment 7 Install the pump in a l...

Страница 12: ...g gradient towards the pump and do not install a gate valve There should be sufficient seals to ensure that air is not sucked in from suction pipe connectors c As shown in Fig 3 avoid convex parts alo...

Страница 13: ...the motor lead wire and the ground Caution With 3 phase motors check that none of the 3 motor terminals is loose or has become separated Phase interrupted operation will result when the equipment is o...

Страница 14: ...laying of the pipes Please install a strainer in the suction side so that alien substance chip of laying of the pipes sand patina and the scale etc doesn t get mixed in a pump at this time I have to d...

Страница 15: ...se Close ball valve after confirming that water comes out from the air vent plug Close the air vent plug Note We have priming set by sold separately without hose Please order 4 When priming manually r...

Страница 16: ...ver operation may result in noise and vibrations Further unnecessary power consumption will result Avoid operation in the state of cavitation occur Over capacity operation may result in cavitation Cav...

Страница 17: ...the pump is out of use for prolonged periods such as the wintertime water inside the pump could freeze causing damage to the pump Accordingly in such situations either drain all water from the pump o...

Страница 18: ...of the motor once a month If insulation resistance is 5M or more it does not interfere with driving When insulation resistance is 1M or less or 5M or more but suddenly decreasing it can be guessed th...

Страница 19: ...nterior bearings Pump size Frequency Hz Mechanical seal Part name Pump size Bearing Sleeve Intermediate casing for bearings 25 50 12 16F 25k EVMS EVMSL 60 12 16F 25k 25 12 16 10 5 21B1 30 6 304 5 21B1...

Страница 20: ...Review the plan Suction head is too high for the pump Discharge head is too high for the pump Review the plan High fluid temperature or volatile fluid Review the plan Cavitation Consult with EBARA Wat...

Страница 21: ...Construction This figure shows a typical model EVML E pump there may be some differences from this figure depending on its model size EBARA has prepared sectional views with the material names for co...

Страница 22: ...1 4 Seal holder 1 111 5 Adjust sleeve 1 115 1 O Ring out casing 2 115 4 O Ring cartridge sleeve 1 115 5 O Ring seal cover 1 120 1 Tie rod 4 120 3 Screw for seal cover 4 120 6 Screw for coupling 4 120...

Страница 23: ...mp remove the drain plug 212 1 for the lower casing 6 3 Remove the cross recessed head machine screws a total of 4 on both sides 130 2 holding the coupling guard 245 and remove the coupling guard 4 Lo...

Страница 24: ...nts on the surface of the mechanical seal s sliding faces 1 Coat the shaft 31 the inside of the cartridge sleeve and the O rings at the mechanical cover 111 3 outside with propylene glycol etc Also if...

Страница 25: ...et screws a total of 3 screws 130 1 9 Secure the motor 800 to the motor bracket with the hexagon bolt 120 13 4 0 kW or less models only Note Rotate the coupling manually and check that the rotation is...

Страница 26: ...e Customs duty and tax in destination are not included And we don t take responsibility to compensate any of secondary loss caused by our pump trouble 3 In following cases replacement and repairing co...