Ebac CD85 Скачать руководство пользователя страница 3

 

 

 

 

Page 3 of 15 

Drawing   : - TPC361 
Issue 

: - 3 

Date 

: - 03/10/12 

 

INTRODUCTION 

 
 

Designed for a wide range of applications, the CD85 dehumidifier is a rugged, 
industrial  unit  which  utilizes  an  energy-efficient  compressor  and  a  compact 
portable design to provide easy efficient drying. 
 
 
The CD85 has a number of special features: 
 
 

 

Compact Size 

 

High efficiency rotary compressor 

 

Ebac’s 

“Hot Gas”

 defrost system 

 

Exterior epoxy powder-coated finish 

 

Provision for permanent drainage 

 

All galvanized interior 

 

Extra long power cord 

 

Humidistat 

 
 
 
The fan draws the moist air through the cold evaporator coil, which cools the 
air below its dew point.  Moisture forms on the evaporator coil and is collected 
in the condensate tray, which is equipped with a permanent drain.  The cooled 
air then passes through the hot condenser coil where it is reheated using the 
same  energy  removed  during  the  cooling  phase,  plus  the  additional  heat 
generated  by  the  compressor.    The  air  is,  therefore,  discharged  from  the 
dehumidifier  at  a  slightly  higher  temperature  with  a  lower  absolute  humidity 
than  that  which  entered.    Continuous  circulation  of  air  through  the 
dehumidifier gradually reduces the relative humidity within the area. 
 
 
The  CD85  dehumidifier  is  a  rugged,  reliable  drying  unit  designed  to  operate 
effectively  over  a  broad  range  of  temperature  and  humidity  conditions.    An 
active  hot  gas  defrost  system,  controlled  by  an  electronic  timer,  guarantees 
positive de-icing, thereby optimizing operation at low temperatures.  
 
 
The unit incorporates a welded and galvanized steel chassis and is finished in 
an epoxy coating for resilience to damage caused by rough handling. 

 

 
 

 

 

E B A C   C D - 8 5    I N D U S T R I A L     D E H U M I D I F I E R 

Pure n Natural Systems  |  purennatural.com  |  1-800-237-9199

Содержание CD85

Страница 1: ...Drawing TPC361 Issue 3 Date 03 10 12 CD85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk E B A C C D 8 5 I N D U S T R I A L D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 8...

Страница 2: ...5 PACKAGE CONTENTS Item Description Quantity 10293GR US Dehumidifier 1 3014338 PVC Tube 12mm I D 3M 3086101 Jubilee clip 1 TPC361 Manual 1 E B A C C D 8 5 I N D U S T R I A L D E H U M I D I F I E R P...

Страница 3: ...ugh the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the deh...

Страница 4: ...M3 hex head bolts Evaporator Grille Cover and Evaporator Blanking Cover are interchangeable Condenser Grille Cover and Condenser Blanking Cover are interchangeable Evaporator and Condenser covers are...

Страница 5: ...Grille Cover Air into Machine Condenser Blank Cover Blocks airflow Evaporator Blank Cover Blocks Airflow Condenser Blank Cover Blocks airflow Evaporator Grille Cover Air into Machine Condenser Grille...

Страница 6: ...dustrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL CD85 HEIGHT 15 75 WIDTH 23 6 DEPTH 13 5...

Страница 7: ...below 80 F an even coating of frost should cover the entire evaporator coil ii If the air temperature is above 80 F frost and or droplets of condensed water should cover the entire evaporator coil F...

Страница 8: ...F the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiri...

Страница 9: ...mped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compres...

Страница 10: ...rant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Facto...

Страница 11: ...198 1 7 Solenoid Coil 3030421 1 8 Capacitor 3030908 1 9 Humidistat 3035147 1 10 Mains Lead 3035148 1 11 Fan Motor 3040262 1 12 Fan Motor Inlet Ring 3040254 1 13 Fan Motor Capacitor 3030893 1 14 Relay...

Страница 12: ...DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARR...

Страница 13: ...Page 13 of 15 Drawing TPC361 Issue 3 Date 03 10 12 E B A C C D 8 5 I N D U S T R I A L D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 800 237 9199...

Страница 14: ...Page 14 of 15 Drawing TPC361 Issue 3 Date 03 10 12 E B A C C D 8 5 I N D U S T R I A L D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 800 237 9199...

Страница 15: ...Date 03 10 12 E B A C C D 8 5 I N D U S T R I A L D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 800 237 9199 Distributed by Pure n Natural Systems Inc PO Box 1137 Streamwood IL 60...

Отзывы: