manualshive.com logo in svg
background image

13

Instruction Booklet 

IB019013EN

Effective March 2019

Zone selective interlocking test kit 

For Digitrip 520M, 520MC and 1150 trip units 

  

EATON

 www.eaton.com

ZSI breaker testing work sheet Digitrip 1150+

The following are the test settings used while programming the 1150+ Digitrip unit. If a parameter setting does not match the one required 

for testing, record it in the space provided, and then modify the setting to match the chart. After testing, remember to change your settings 

back to the states you record below. 

Setting (required for testing)            Original setting

Setting (required for testing)             Original setting

Curve type (LSIG**) ____________________________________

Ground slope** (flat) ____________________________________

Long slope (I

2

T) ________________________________________

Ground time (0.30 sec) __________________________________

Long PU (0.4 sec) ______________________________________

Amp unbalance (off) ____________________________________

Long time @ 6 X Ir (2.0 sec) _____________________________

Amp unbalance time (10 sec) ____________________________

Long memory (off)  _____________________________________

Phase loss (off)  ________________________________________

Short slope (flat)________________________________________

Main PU (10 x 

l

n

) _______________________________________

Short PU (3.0 x 

l

r

) _______________________________________

Maintenance mode (disabled) ____________________________

Short time Z1* (0.50 sec) ________________________________

Frequency (60 Hz) ______________________________________

Short time Z2* (0.30 sec) _______________________________

BC relay reset (auto) ____________________________________

Short time Z3* (0.10 sec) ________________________________

Sliding demand (off) ____________________________________

Inst PU (4 x 

l

n

) __________________________________________

Wave form capture (off) _________________________________

Gnd PU (0.3) ___________________________________________

Rev power sensing (disabled) ____________________________

                                                                          Breaker name: __________ Breaker position: ___________

Setting (required for testing)             Original setting

Setting (required for testing)             Original setting

Curve type (LSIG**) ____________________________________

Ground slope** (flat) ____________________________________

Long slope (I

2

T) ________________________________________

Ground time (0.30 sec) __________________________________

Long PU (0.4 sec) ______________________________________

Amp unbalance (off) ____________________________________

Long time @ 6 X Ir (2.0 sec) _____________________________

Amp unbalance time (10 sec) ____________________________

Long memory (off)  _____________________________________

Phase loss (off)  ________________________________________

Short slope (flat)________________________________________

Main PU (10 x 

l

n

) _______________________________________

Short PU (3.0 x 

l

r

) _______________________________________

Maintenance mode (disabled) ____________________________

Short time Z1* (0.50 sec) ________________________________

Frequency (60 Hz) ______________________________________

Short time Z2* (0.30 sec) _______________________________

BC relay reset (auto) ____________________________________

Short time Z3* (0.10 sec) ________________________________

Sliding demand (off) ____________________________________

Inst PU (4 x 

l

n

) __________________________________________

Wave form capture (off) _________________________________

Gnd PU (0.3) ___________________________________________

Rev power sensing (disabled) ____________________________

                                                           

Breaker name: __________ Breaker position: __________

_

*  Assuming Z1 is connected to main, Z2 is directly downstream of Z1, and Z3 is directly downstream of Z2.
**  If supplied.

Содержание ZSI

Страница 1: ...TRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT m CAUTION SPECIFIC OPERATING PROCEDURES MUST BE DEVELOPED BY THE RESPONSIBLE PARTY DUE THE UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM AND USER REQUIREMENTS FAILURE TO DEVELOP SPECIFIC PROCEDURES COULD LEAD TO IMPROPER USE OR OTHER MORE SERIOUS CONSEQUENCES m CAUTION PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING TO O...

Страница 2: ...ound time 0 3 sec Amp unbalance Off Amp unbalance time 10 sec Phase loss OFF Main PU 10 x In Maintenance mode Disabled Frequency 60 HZ BC relay reset Auto Sliding demand Off Wave form capture Off Rev power sensing Disabled Table 2 Digitrip 520M 520MC settings Parameter Setting Parameter Setting Long delay setting 0 4 Long delay time 6xlr 2 Short delay setting 3 Short delay time Depends on zone Z1 ...

Страница 3: ... the power cable into the ZSI test box 5 Plug the power cable into a standard 120V outlet 6 Refer to the Test Sequence screen in the Navigating the HMI Screens section to determine which series of tests need to be performed 7 Refer to the Zone Configurations section to determine the correct cable connections for the desired test 8 Plug a ZSI zone cable into one of the zone plugs on the ZSI test bo...

Страница 4: ... the correct zone 13 Move the selector switch on the ZSI test box to the ON posi tion 14 Navigate to the Test Screen on the display panel 15 Select Single or Double based on the switchgear configura tion being tested 16 Select Main Fault Tie Fault or Feeder Fault 17 Press the Initiate Test button to start the test 18 After the test is completed press the Reset Test button to prepare the tester for...

Страница 5: ...n the selections made on the HMI Circuit diagrams of these setups can be found in the Zone Config screen subsection of the Navigating the HMI Screens section in this manual Note N For M T T M repeat test for each tie breaker ZSI Test Box Zone 1 Zone 2 Zone 3 Main1 Digitrip Tie Digitrip Main2 Feeder Digitrip Configuration 1 Main Tie Main Configuration 1 Arrangement double Main fault This simulates ...

Страница 6: ...iguration 2 Main Tie Main Configuration 2 Arrangement double Main fault This simulates a fault originating between the M2 main 2 breaker and the tie breaker Tie fault This simulates a fault originating downstream of the M2 main 2 breaker and tie breaker Feeder fault This simulates a fault originating on the load side of a feeder on the main 1 bus main 1 feeder This fault would flow through main 2 ...

Страница 7: ...Main fault This simulates a fault originating on the load side of the main 1 breaker Feeder fault This simulates a fault originating on the load side of the main 1 feeder breaker ZSI Test Box Zone 1 Zone 2 Zone 3 Main2 Digitrip Main2 Feeder Digitrip Configuration 4 Main2 Main2 Feeder Configuration 4 Arrangement single Main fault This simulates a fault originating on the load side of the main 2 bre...

Страница 8: ...double main opposite feeder Simultaneous main fault This simulates simultaneous faults One originates on the load side of the main 1 breaker before the tie and the other originates on the load side of the main 2 feeder ZSI Test Box Zone 1 Zone 2 Zone 3 Main2 Digitrip Main1 Feeder Digitrip Configuration 6 Simultaneous Main Fault Main1 Digitrip Configuration 6 Arrangement double main opposite feeder...

Страница 9: ...ections Once the check box has been selected the Test Screen button becomes visible Digitrip settings screen The Digitrip Settings button will take you to the Digitrip settings screen shown below Here you can select which Digitrip model you are testing and find all of the settings required to be enabled on the trip units in order to successfully test them using the ZSI test box Zone configuration ...

Страница 10: ...see 5 5 This area of the screen is where buttons are that allow a user to change the arrangement of the switchgear lineup being tested 6 After a test is performed this area displays a timer that is relative and useful when troubleshooting any issues related to the wiring of the test box These are not true trip times but can be used to determine ZSI functionality 7 This is the area where the test r...

Страница 11: ...p plugs are installed in correct breakers Single double feeder tie Z1 tripped during Z2 test Check trip unit settings and ZSI configuration map to ensure trip plugs are installed in correct breakers Double tie Z3 tripped during Z2 test Check trip unit settings and ZSI configuration map to ensure trip plugs are installed in correct breakers Z3 error messages Double feeder fault Z3 trippped too slow...

Страница 12: ...______________________________ Ground time 0 4 ________________________________________ Arc flash reduction off __________________________________ Arc flash reduction setting R5 ___________________________ Long delay time 6xlr 2 ________________________________ Breaker Name _______ Breaker Position ________ Setting required for testing Original setting Setting required for testing Original setting...

Страница 13: ...__________________ Inst PU 4 x ln ___________________________________________ Wave form capture off __________________________________ Gnd PU 0 3 ____________________________________________ Rev power sensing disabled _____________________________ Breaker name __________ Breaker position ___________ Setting required for testing Original setting Setting required for testing Original setting Curve t...

Страница 14: ...ractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY...

Отзывы: