5 Installation
5.2 Requirements for the place of installation
26
MICRO PANEL XV400 10.4"/12.1"/15"
12/2010 MN04802010Z-EN
www.eaton.com
5.2
Requirements for the place of installation
Approvals:
The device must only be used in locations that are approved for the device. See the markings on
the nameplate and Chapter 9 Technical data,
67.
Power supply:
The power supply must comply with the requirements stated in Chapter 9.5.1 Power supply,
75.
5.2.1
Requirements for use in EX Zone 1 and 2
The following requirements must be fulfilled in order for a device to be used in EX Zone 1 and 2:
The device must have a stainless steel front.
The device must be mounted in a pressurized housing that has an EC type certificate for Ex px
(pressurized enclosure).
The device is mounted with the sealing strip and eight retaining brackets (supplied).
Ambient temperature range: 0°C
≤
Ta
≤
+50°C
(maximum surface temperatures: front 70°C / electronics 110°C)
Max. permissible pressure: 10 mbar continuous and during rinsing 30 mbar
All instructions in this document must be observed.
5.2.2
Engineering conditions of acceptability by Underwriters Labaratories Inc. (UL)
The device must be installed in an end-product. Consideration must be given to the following:
The environment of the device must comply with pollution degree 2.
The device must be supplied via a SELV source.
The device must be connected to the protective earth of the end-product (the functional earthing
connection of the power supply interface must be connected).
In order to protect the device from potential internet threats, it should be connected to Ethernet
networks that are isolated from the internet or safety protected and isolated from the Corpo-
rate/Enterprise network by a firewall or router.
Fire protection and electrical protection must be ensured via the end-product (not required for the
front of the device).
5.2.3
Requirements for the mounting position
The device is designed for mounting in control cabinets, control panels or control desks. 10.4" and 12.1"
devices can be mounted horizontally or vertically, 15" devices must only be mounted horizontally. The
following requirements must be fulfilled when selecting a suitable mounting position:
The display should not be exposed to direct sunlight (the UV component of sunlight reduces the
lifespan of the device and disturbs the infra-red touch sensor).
If the device is to be used in potentially explosive atmospheres, the device must not be subjected
to hazardous knocks.
The operating elements on the service side of the device and the cable connections are accessible
after the device has been mounted.
The ambient conditions stated must be observed. See Chapter 9.9 Ambient conditions,
79.
Sufficient ventilation (cooling) must be ensured by means of:
Clearance of at least 3 cm to the ventilation slots
Содержание XV400
Страница 6: ...Contents 6 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com ...
Страница 14: ...2 Device description 2 7 Designation 14 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com ...
Страница 54: ...5 Installation 5 4 Mounting 54 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com ...
Страница 80: ...9 Technical data 9 9 Ambient conditions 80 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com ...