5 Installation
5.4 Mounting
46
MICRO PANEL XV400 10.4"/12.1"/15"
12/2010 MN04802010Z-EN
www.eaton.com
5.4.3
Mounting a device with 4-hole front
1
Select the mounting position of the device as described in Chapter 5.2.3 Requirements for the
mounting position,
26.
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
10.4" devices: 314
×
238 mm (±1 mm)
12.1" devices: 344
×
262 mm (±1 mm)
15" devices: 410
×
315 mm (±1 mm)
Four through holes ø 5.5 mm, with the following distances apart:
10.4" devices: From 326 mm (±0.2 mm) to 240 mm (±0.2 mm)
12.1" devices: From 360 mm (±0.2 mm) to 254 mm (±0.2 mm)
Four through holes ø 6.5 mm, with the following distances apart:
15" devices: From 430 mm (±0.2 mm) to 290 mm (±0.2 mm)
Material thickness at the mounting cutout 2…20 mm
An optional counter frame is required for mounting in accordance with IP65 and for
use in potentially explosive atmospheres. Please contact your supplier.
10.4" and 12.1" devices can be mounted horizontally or vertically, 15" devices must
only be mounted horizontally.
Fig. 31 Mounting cutout for 10.4" devices
Fig. 32 Mounting cutout for 12.1" devices
240.0
+0.2/-0.2
326.0
+0.2/-0.2
314.0
+1/-1
238.0
+1/-1
ø
5.5
254.0
+0.2/-0.2
360.0
+0.2/-0.2
344.0
+1/-1
262.0
+1/-1
ø
5.5
Содержание XV400 10.4"
Страница 6: ...Contents 6 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com...
Страница 14: ...2 Device description 2 7 Designation 14 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com...
Страница 54: ...5 Installation 5 4 Mounting 54 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com...
Страница 80: ...9 Technical data 9 9 Ambient conditions 80 MICRO PANEL XV400 10 4 12 1 15 12 2010 MN04802010Z EN www eaton com...