6. Interferences
6. Interferences
This section provides troubleshooting information for your XV300 in case it does not
behave as expected.
Fault
Cause
Remedy
XV300 will not boot up
No 24 VDC supply voltage
Check the input wiring.
Switch on XV300
The display stays or
turns dark.
The backlight is deactivated.
Switch the backlight on; please
refer to the Windows Embedded
Compact 7 pro system description
or to the corresponding function
in the visualization software.
The Capacitive multi-
touch technology (PCT)
is not responding or is
responding incorrectly
when used.
The functional earthing has not been
connected properly.
The XV300 needs to be connected
to the conductive structure in,
e.g., the control panel using the
central earth point (earthing
screw).
Ground connection char-
acteristics:
Wire cross-sectional area ≧ 1.5
mm², length ≦ 350 mm
The touch is not calibrated correctly.
Switch on XV300
Calibrate the touch functionality;
please refer to the Windows
Embedded Compact 7 pro system
description
The touch is disabled.
Switch on XV300
Enable the touch functionality;
please refer to the Windows
Embedded Compact 7 pro system
description