5 Installation
5.3 Interfaces
30
MICRO PANEL XV-112
11/2011 MN04802005Z-EN
www.eaton.com
5.3.8
CAN
If the CAN interface is electrically isolated, depends on the device version. See Chapter 2.3 Device
versions,
Tab. 10 Pin assignment of CAN interface in accordance with CiA
CAUTION
Non-isolated interfaces
The device may be damaged due to potential differences.
The GND terminals of all bus stations must be connected.
Fig. 13 CAN interface (9-pin, D-Sub, male, UNC)
Pin
Signal
Assignment
1
-
nc
2
CAN-L
Bus line (dominant low)
3
CAN-GND
CAN Ground
4
-
nc
5
-
nc
6
GND
Optional CAN Ground
7
CAN-H
Bus line (dominant high)
8
-
nc
9
-
nc
Pin 3 (CAN-GND) and 6 (GND) are connected internally in the device.
nc: Pins 1, 4, 5, 8 and 9 must not be connected.
The CAN bus drivers are fed internally with power.
No power supply for third-party devices is implemented on the CAN connector.
1 2 3 4 5
6 7 8 9
Содержание XV-112
Страница 1: ...Operating Instructions 11 2011 MN04802005Z EN XV 112 MICRO PANEL...
Страница 6: ...1 General 1 3 Additional documentation 6 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...
Страница 16: ...3 Safety regulations 3 4 Device related hazards 16 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...
Страница 18: ...4 Operating and indication elements 4 1 Overview 18 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...
Страница 38: ...5 Installation 5 4 Mounting 38 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...
Страница 42: ...6 Operation 6 4 Inserting and removing an SD card 42 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...
Страница 56: ...9 Technical data 9 9 Ambient conditions 56 MICRO PANEL XV 112 11 2011 MN04802005Z EN www eaton com...