20 Analog input module XN-322-4AI-PTNI
20.3 Wiring
138
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
20.3.1 Two-wire connection
When using a 2-wire configuration, the resistance value between pins 1 and
3 will be measured and interpreted as a temperature reading. The cable
resistance will affect the reading in the form of an error. The advantage of
using this type of configuration is the fact that it requires a small number of
connection cables.
R
L
= Cable resistance of connection cable
R
T
= Resistance of temperature sensor
Figure 79:
Wiring diagram for two-wire connections; X1, X2, X3, and/or X4 can be used with
this type of configuration
20.3.2 Three-wire connection
When using a three-wire connection, the resistance value between pins 1
and 3 and between pins 1 and 2 is measured. In this type of configuration,
the cable resistance will not affect the measurement, provided all cable
lengths are identical.
R
L
≤
200
Ω
= Cable resistance of connection cable
R
T
= Resistance of temperature sensor
X1
R+ S+ R-
X2
R+ S+ R-
R+ S+ R-
R+ S+ R-
X3
X4
PE
24 V
0 V
R
L
R
L
R
T
R
L
R
L
R
T
R
L
R
L
R
T
R
L
R
L
R
T