2
Technical Data
TD450157EN
Effective
August 2022
Eluxa horns, horn strobes, & strobes
EATON
www.eaton.com
Features
•
Energy efficient
•
LED technology provides industry’s lowest current draw
•
Fewer power supplies required, smaller wire gage, reduced
wire runs
•
Low-profile design
•
One of the smallest, most compact single-gang designs
•
Sleek, modern aesthetics with no visible mounting screws
•
Special lettering available
•
6 Field selectable settings in 1 device
•
Wall: 15, 30, 75, 110, 135, 185 cd
•
Ceiling: 15, 30, 75, 110, 150, 177 cd
•
3 horn patterns
•
Continuous, T3, and T3/T4; Fire and CO signaling in 1 device
•
Sound pressure (Anechoic) dBA
•
Low 86, High 91 (for Continuous, T3, and T4)
•
Easy-to-install
•
Mounting plate included with all models: Convenient capture
hinge allows installers to easily hold the device while fastening
the single-mount screw in place.
•
Pre-wire/pre-test capability to check for wiring and ground
faults prior to appliance installation
•
Finger slide switches--No tools needed for setting changes
•
IN/OUT screw terminals using #12 to #18 AWG wires
•
Mounting options include ELSBB, any single-gang backbox and
to 4” square with adapter kit for wall models and LSPKBB-C
backboxes and 4” square, 1 1/2” or 2 1/8”deep for ceiling
•
Strobe synchronization
•
Meet synchronizing standards with Wheelock’s DSM Sync
Modules, PS Power Supplies or SAFEPATH products
•
Ability to mix xenon and LED strobes in the same field of view
•
Compliance
•
NFPA 72 2016 - 20 ms flash duration requirements
•
UL 1971, UL 1638, UL 464, ULC-S525, ULC-S526
•
California State Fire Marshal (CSFM)
•
Factory Mutual (FM)
•
RoHS
•
FCC Part 15, ICES
ote:
N
Please read these specifications and associated installation instruc-
tions, before using, specifying, or installing this product. Visit Eaton.com/
Lifesafetynotification for current installation instructions.
General Notes
•
Strobes are designed to flash at 1 flash per second minimum over
their “Regulated Voltage Range.” Note that NFPA-72 specifies a
flash rate of 1 to 2 flashes per second and ADA Guidelines specify
a flash rate of 1 to 3 flashes per second.
•
All candela ratings represent minimum effective strobe intensity
based on UL 1971.
Drawings
Figure 1. Wall, horn strobe
Figure 2. Ceiling, horn strobe
Eluxa Horns
Model
Regulated Voltage
Range VDC
High
dB
Low
dB
ELHN/ELHNC
ELHN/ELHNC
8.0 - 17.5
16.0 - 33.0
0.025
0.028
0.020
0.021
Table 1. Horn ratings per UL/ULC Anechoic