background image

1

2

3

4

5

6

7
8
9

10

11

12

13

14

15

16

17

18

Technical Data  

TD534-0501002U

Instructions for the Installation,

Operation and Maintenance

of W-SLC-7.2

Effective January 2013

Product structure and working principles

Basic device structure

The truck assembly is arranged into upper and lower sections, including fuses, a medium voltage vacuum contactor, a specific cradle and 
related interlocking devices. See Figure 1. 

1. Manual secondary disconnect

2. Fuse holder

3. Fuse holder cover

4. Nameplate

5. Flexible shunt

6. Insulated interlock bar

7. Fuse status indicator

8. Opening button

9. Opening and closing status

10. Counter

11. Primary disconnect

12. Movable fuse holder cover

13. Fuse

14. Lower contact arm

15. Support plate for lower 
      contact arm

16. Vacuum interrupter

17. Mechanical latching device 

18. Withdrawable cradle

Figure 1

Operation principle

The W-SLC utilizes Eaton vacuum interrupters that exhibit both a 
long electrical life and a high interruption capability. 
An electromagnetic operating mechanism makes the contactor 
close, while an optional latching mechanism keeps the contactor 
closed as well as compresses the opening spring ready for tripping 
the contactor at the opening signal. For contactors with mechanical 
latch, there are two operating coils, closing and opening coils. To 
close the contactor a pulse signal is sent to the closing coil and to 
open the contactor a pulse signal is sent to the opening coil.
An electronic counter on the front of the unit automatically keeps a 
record of the number of operations (open and close) of the 
contactor.

Cradle interlocking

The cradle of the unit is interlocked such that the contactor cannot 
be closed if the truck is not racked into the ‘Service’ position. The 
cradle is also interlocked with the enclosure door such that it cannot 
be racked in with the door open nor can the door be opened are 
provided with the unit racked into the ‘Service’ position. Further 
interlocks with the earth switch such that the earth switch cannot 
be closed with the unit in the ‘Service’ position and the unit cannot 
be racked into the ‘Service’ position with the earth switch in the 
Closed position.

Fuse interlocking

The device has an interlocking tripping mechanism to provide 
‘Fuse Blown’ and ‘Fuse Not Fitted’ indication on the front of the 
unit. This mechanism has auxiliary contacts which are used to 
prevent the contactor from closing in the event there is no fuse or 
a fuse is blown. Additional contacts are available for remote 
indication of Fuse Blown or Fuse Not Fitted.

3

EATON CORPORATION

www.eaton.com

Содержание W-SLC-7.2

Страница 1: ...ation and technical data Product structure and working principles Main device structure Operation principles Fuse interlocking Cradle interlocking Dimensions Schematic wiring diagram Mounting commissioning and operating Receiving handling and storage Commissioning and operating Maintenance Inspection of vacuum interrupter Inspection of contact s wear out Inspection of mechanisms Usage of fuses Rep...

Страница 2: ... 66 6 NO 6 NC Coil voltage 120 60 Hz 240 60 Hz 110 50 Hz 220 50 Hz 110 DC 220 DC A B U W X Y Mechanical latch Coil voltage 0 4 5 None 110 50 120 60 Hz 220 50 240 60 Hz IEC SL contactor 7 2 kV 400 A Coil drop out time 30 ms 50 ms 130 ms 250 ms 330 ms 5 6 7 8 9 W SLC 1 SLC014S 5 Y 66 5 with fuses fuses replaced by conductors 1 0 Note fuses are supplied by user IEC 60470 2000 High Voltage Alternative...

Страница 3: ...um breaking capacity Rated load and overload characteristics Rated load and overload characteristics Take over current for release operated combination Main loop resistance Closing time Opening time Electrical life category AC3 and AC4 Mechanical life Control Power Supply Auxiliary contact ratings Utilization category Power frequency withstand voltage 1min Lightning withstand voltage 25 opening op...

Страница 4: ...the opening signal For contactors with mechanical latch there are two operating coils closing and opening coils To close the contactor a pulse signal is sent to the closing coil and to open the contactor a pulse signal is sent to the opening coil An electronic counter on the front of the unit automatically keeps a record of the number of operations open and close of the contactor Cradle interlocki...

Страница 5: ...002U Instructions for the Installation Operation and Maintenance of W SLC 7 2 Effective January 2013 Figure 2 Dimensions Please refer to Figure 2 for W SLC dimensions Note dimension unit mm 4 EATON CORPORATION www eaton com A A ...

Страница 6: ...ng diagram The wiring diagrams Fig 3 and Fig 4 show the unit in the withdrawn position and the contactor open The diagram is for reference only please refer to the wiring diagram with the product for most accurate information as customer specific wiring may have been included for a specific purpose Figure 3 5 EATON CORPORATION www eaton com ...

Страница 7: ...Technical Data TD534 0501002U Instructions for the Installation Operation and Maintenance of W SLC 7 2 Effective January 2013 Figure 4 6 EATON CORPORATION www eaton com ...

Страница 8: ...osition or testing position c Interlock mechanism is used to prevent the racking handle operating with the door open d Interlock mechanism is used to prevent the compartment door opening with the unit in the Service position 2 Connect the secondary connector and apply secondary power and operate the contactor according to procedures Then check whether opening and closing position indicator is work...

Страница 9: ...ral times to ensure smooth operation All the parts which need lubrication are lubricated before shipping However if the lubricants have degraded it may be essential to lubricate the parts during annual inspection Usage of fuses Before putting into use check the fuse appearance for completeness wellness cleanness and correct mounting direction The striker pin should be facing the front of the unit ...

Страница 10: ...ce people in order to make proper adjustments 3 If users need to conduct parameter testing for the W SLC please pay attention to following notices 3 Use special tool the part No is 534 8161200 for assembling fuse tube to remove movable fuse holder cover see Figure 8 4 Put on clean electrician gloves and remove the fuse see Figure 9 5 Check the sliding connecting spring contact fingers on both ends...

Страница 11: ...with expertise in power distribution and circuit protection backup power protection control and automation lighting and security structural solutions and wiring devices solutions for harsh and hazardous environments and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a diversified power management...

Отзывы: