background image

14

Instruction Booklet 

IB131006EN

Effective March 2019

Instructions for installation,  

operation, and maintenance of type  

VCP-W vacuum circuit breakers 

EATON

 www.eaton.com

Outdoor storage of the breaker element is NOT recommended.  

If unavoidable, the outdoor location must be well drained and a 

temporary shelter from sun, rain, snow, corrosive fumes, dirt, falling 

objects, and excessive moisture must be provided.  Containers 

should be arranged to permit free circulation of air on all sides 

and temporary heaters should be used to minimize condensation.  

Moisture can cause rusting of metal parts and deterioration of high 

voltage insulation.  A heat level of approximately 400 watts for each 

100 cubic feet (2.83 cubic meters) of volume is recommended with 

the heaters distributed uniformly throughout the structure near the 

floor.
Indoor storage should be in a building with sufficient heat and air 

circulation to prevent condensation.  If the building is not heated, the 

same general rule for heat as for outdoor storage should be applied.

3.5 Tools and accessories

Tools and accessories, both standard and optional, are available for 

use with the circuit breaker element (Figure 3).  If not specified 

accessories can be used for 36 in. wide and 26 in. wide breakers.

Spin-free levering-in crank:

 Used to crank breaker between 

DISCONNECT, TEST, and CONNECTED positions.

Extension rails:

 Permits breaker to be withdrawn from its compart-

ment.

Rail clamps:

 Used to secure breaker to extension rails.

Lifting yoke:

 Used to lift breaker.

Manual charging handle:

 Used to charge closing springs manually.

Portable lifter:

 Used to lift breaker to or from extended rails.

Breaker lift pan:

 This accessory enables the breaker to be lifted 

from the ground to any height cell without the extension rails.  It 

consists of a portable lifter and a MV breaker lift pan.

• 

Portable lifter;

• 

MV breaker lift pan with short extension rail kit for 36”or 26” wide 

breaker.

Drawout ramp:

 Used to insert or withdraw breaker from lower 

compartment without portable lifter.

Docking transport dolly:

 Used to insert or withdraw breaker from 

lower compartment without portable lifter or move breaker from one 

location to another.

Electrical levering-in device:

BPI pan assembly:

Integral Motorized Racking (MR2) used to electrically move 

breaker between DISCONNECT/TEST, or DISCONNECT, TEST, and 

CONNECTED positions is available. Specified by description as 

opposed to a style number.
If the external electric levering-in device which mounts to the door or 

pan assembly is used, then the breaker can be moved between the 

DISCONNECT and CONNECTED positions.
The process of levering the breaker from the DISCONNECT to the 

TEST position would need to be performed manually (approximately 

6 turns).

Non-BPI pan assembly:

Used to electrically move the breaker between DISCONNECT/TEST 

and CONNECTED positions.

Truck operated cell (TOC) switch: 

Indicates when breaker is in the 

CONNECT position.  Furnished with standard push on wire termi-

nals. Optional ring tongue terminals are available.

Mechanism operated cell (MOC) switch: 

Provides additional 

normally open and closed contacts for when control and protection 

scheme exceeds the available auxiliary contacts in the breaker. 

Furnished with standard push on wire terminals. Optional ring 

tongue terminals are available.  
This feature is available in two different configurations:
1.) Functions in both the TEST and CONNECT positions, or 
2.) Functions only in the CONNECT position. 
Eaton strongly recommends use of the TEST and CONNECT position 

configuration.

Test jumper:

 Used to operate breaker electrically while breaker is on 

extension rails or transport dolly.

Test cabinet:

 Used to provide power to operate breaker outside its 

compartment for the purpose of testing functionality.

Key provisions with positional interlock:

 This enables locking of 

the levering-in cage when the breaker is in the TEST position with a 

padlock or keyed cylinder lock.

Wheel conversion kit (MG & TD only): 

Due to how the manual 

ground and test device is designed this is the best direct roll-in 

wheel kit to use.

Wheel conversion kit for direct roll-in:

 This wheel kit can be used 

to convert a standard breaker or electrical ground and test device to 

a direct roll-in version.

Conversion kit ROF to non-ROF: 

This kit is used to convert a direct 

roll-in cell to a non direct roll-in cell.  It provides the teeter totter 

feature that prevents removing a breaker from the breaker cell when 

the extension rails or MV breaker lift pan are not in place.  Also, 

the short ramp feature in the front of each rail would need to be 

removed.

Conversion kit non-ROF to ROF:

 This kit is used to convert a non-

direct roll-in cell to a direct roll-in cell.  It provides the ramp feature 

that goes on the end of each rail to help guide the steel wheels on 

the side of the breaker up onto the rail rolling surface.  This is only 

to be used in the lower switchgear cells that are level with the floor.  

The teeter totter feature that keeps the breaker from being rolled out 

of the cell would need to be removed.

Secondary conversion kit:

 This kit converts an automatic secondary 

in a BPI pan assembly to a manual enabled automatic secondary.  

When the release lever is raised above the stop feature the second-

aries will slide forward to automatically connect, see section 8.2 for 

more details.

Closed door racking guide:

 This feature can be added to the front 

of the BPI pan assembly to provide a guide for the manual levering-

in tool when the switchgear door is closed to guide the levering-in 

crank socket onto the levering-in drive screw nut.

Содержание VCP-W Series

Страница 1: ...Instruction Booklet IB131006EN Effective March 2019 Supersedes July 2017 Instructions for installation operation and maintenance of type VCP W vacuum circuit breakers...

Страница 2: ...HIN THEIR NAMEPLATE RATINGS OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE ALL SAFETY CODES SAFETY STANDARDS AND OR R...

Страница 3: ...pter integrity 28 4 4 Insulation 28 4 5 Contact erosion and wipe 28 4 6 Primary circuit resistance 28 4 7 Nameplate 28 4 8 Electrical operation check 28 4 8 1 Circuit breaker insertion and removal 28...

Страница 4: ...aker outlines dim in inches mm 11 Figure 2 Type VCPW ND circuit breaker outlines and dimensions in inches mm 12 Figure 3 Typical VCP W tools and accessories 23 Figure 4 Typical front view VCP W vacuum...

Страница 5: ...trical current basis 8 Table 3 ANSI Standards type VCP WC extra capability vacuum circuit breaker 5 27 kV rated symmetrical current basis 9 Table 4 IEC 56 Standardsa type VCP W vacuum circuit breaker...

Страница 6: ...LDFACE AS SHOWN BELOW m CAUTION COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION OPERATION OR APPLICATION OF THE EQUIPMENT IN ADDITION ONLY QUALIFI...

Страница 7: ...MVA kV rms kV rms Amperes kA rms Cycles Seconds kV rms kA rms kA peak kA rms 50VCPW ND250 4 16 250 4 76 1 24 19 60 1200 29 5 2 3 85 36 97 58 50VCP W250 4 16 250 4 76 1 24 19 60 1200 2000 3000 29 5 2 3...

Страница 8: ...tor switching cable charging Power frequency 1 min Impulse kV MVA kV rms kV rms Amperes kA rms Cycles Seconds kV rms kA rms kA peak kA rms 270VCP W750 16 e 27 750 27 1 0 60 125 600 1200 2000 16 5 2 51...

Страница 9: ...1600i 7 7 7 7 7 7 465 465 465 10 000 10 000 10 000 270 VCP W 25C 27 1 60 125 1200 1600 25 75 36 85 25 h 3 2 1 1 400 20 4 2 2 500 270 VCP W 32C 27 1 60 125 1200 1600 31 5 57 40 97 32 g 3 1 1 1 400 20...

Страница 10: ...15 0 164 98 a All circuit breakers are tested to 60 Hz however they can also be applied at 50 Hz with no derating b Consult the Consulting Application Guide CA08104001E sections 1 and 5 for further i...

Страница 11: ...VCPW SE and VCP WC circuit breaker outlines and dimensions in inches mm Breaker Identification A B C D E 240 VCP W 270 VCP W 270 VCP WC 10 254 00 14 355 60 16 25 412 75 34 80 883 92 35 22 894 59 50 3...

Страница 12: ...enance of type VCP W vacuum circuit breakers EATON www eaton com Figure 2 Type VCPW ND circuit breaker outlines and dimensions in inches mm 21 38 543 05 7 00 177 80 7 00 177 80 3 69 93 73 20 88 530 35...

Страница 13: ...aker element is not to be used immediately but is to be placed in storage maximum protection can be obtained by keeping it packed as shipped Upon receipt of the equipment inspect the containers for an...

Страница 14: ...to be performed manually approximately 6 turns Non BPI pan assembly Used to electrically move the breaker between DISCONNECT TEST and CONNECTED positions Truck operated cell TOC switch Indicates when...

Страница 15: ...and left one set 7813C41G03 Set of rail clamps 6511C83G11 Lifting yoke 691C607G11 Manual charging handle 8064A02G11 Standard set of accessories Spin free levering in crank with clutch Extension rails...

Страница 16: ...Manual charging handle 8064A02G11 Set of ND accessories Spin free levering in crank with clutch Primary contact spanner wrench Extension rails right and left one set Manual charging handle Set of rai...

Страница 17: ...7G11 Manual charging handle 8064A02G11 Standard set of 27 kV accessories Levering in crank with clutch manual charging handle 1A30136G02 Wheel kit for direct roll in 68C5010G42 Portable lifter 1C19086...

Страница 18: ...terminals only 3000 A 66A5092G46 66A5092G06 66A5092G16 Lower terminals only 3000 A 66A5092G47 66A5092G07 66A5092G17 Upper and lower terminals 1200 2000 A with ROF wheels installed 66A5092G82 66A5092G6...

Страница 19: ...302G26 3000 A 250 Vdc or 240 Vac 66A5302G27 1200 2000 3000 A 48 Vdc 66A5302G32 1200 2000 3000 A 125 Vdc or 120 Vac 66A5302G33 1200 2000 3000 A 250 Vdc or 240 Vac 66A5302G34 With roll on floor wheels R...

Страница 20: ...vice for VCP WXC Description Style number Electrically operated ground and test device Upper terminal 1200 2000 3000 A 125 Vdc or 120 Vac 63 kA 66A5302G83 Lower terminal 1200 2000 3000 A 125 Vdc or 12...

Страница 21: ...20 Table 18 VCP W ANSI rated breaker weightsa Rating Amperes Lbs kg 50VCPW ND250 1200 345 157 50VCP W250 50VCPW SE250 1200 2000 3000 350 159 410 186 525 238 50VCP W350 50VCPW SE350 1200 2000 3000 460...

Страница 22: ...2000 375 170 410 186 175VCP W25 630 1250 2000 350 159 350 159 410 186 175VCP W32 1250 2000 375 170 410 186 175VCP W40 1250 2000 375 170 410 186 240 VCP W1 6 630 1250 2000 462 210 484 220 506 230 240...

Страница 23: ...installation operation and maintenance of type VCP W vacuum circuit breakers EATON www eaton com Figure 3 Typical VCP W tools and accessories Note products shown for representation only New products...

Страница 24: ...cuum circuit breakers EATON www eaton com Figure 4 Typical front view VCP W vacuum circuit breaker See Figure 45 for an example of a roll on the floor wheel kit 1 Front panel 2 Lift pull handle 3 Whee...

Страница 25: ...front cover removed 1 L H closing spring 2 Anti pump relay 3 Auxiliary switch 4 Motor cutoff switch 5 Closing cam 6 Spring release close coil assembly 7 Shunt trip assembly 8 Charging motor 9 Chargin...

Страница 26: ...ce of type VCP W vacuum circuit breakers EATON www eaton com Figure 6 Typical rear view VCP W vacuum circuit breaker element 1 Vacuum interrupter 2 Phase barrier 3 V flex current transfer system 4 Dir...

Страница 27: ...type VCP W vacuum circuit breakers EATON www eaton com Figure 7 Typical VCP W vacuum circuit breaker front cover arrangement 1 Front panel 2 Nameplate 3 Operation counter 4 Open closed indicator 5 Ma...

Страница 28: ...secondary insulation as described in Section 6 4 5 Contact erosion and wipe Manually charge the closing springs and close the circuit breaker Check contact erosion and wipe as described in Section 6 4...

Страница 29: ...res 9 and 10 Figure 9 Insertion of the drawout extension rails Figure 10 Lifting and setting the breaker in the housing Checking pan operation A TEST or DISCONNECT TEST position To operate the breaker...

Страница 30: ...hex drive nut on the levering system In order to engage the hex drive nut you must push in the levering system slider 3 Rotate the levering in crank in a counterclockwise direction until the breaker...

Страница 31: ...31006EN Effective March 2019 Instructions for installation operation and maintenance of type VCP W vacuum circuit breakers EATON www eaton com Note N The legend for Figures 12 and 13 follow Figure 13...

Страница 32: ...n BPI pan assembly 1 2 4 5 7 6 9 8 3 Legends for Figures 12 13 1 Ground contacts 2 Levering system 3 Automatic BPI or manual non BPI secondary 4 Racking screw 5 Moving block 6 Slider 7 Breaker positio...

Страница 33: ...pping of a closed breaker by pushing in on the slider item 6 that prevents access to the racking screw Non BPI pan assembly Figure 13 displays the Z shaped slider interlock that prevents a closed brea...

Страница 34: ...mpartment There is also a coding plate fastened to the front of the breaker If the breaker has a lower interrupting rating than the rating of the compartment or if the voltage and continuous current c...

Страница 35: ...ional Figure 46 It will function the same as the Non BPI pan assembly above due to the replacement of the L bracket with the Z bracket Negative interlock The negative interlock prevents the circuit br...

Страница 36: ...position Engage the extension rails Once again disengage the levering latch and pull the circuit breaker out The circuit breaker will trip close and trip as it comes out on to the extension rails fro...

Страница 37: ...that the interrupter must be replaced observe the erosion mark placed on each moving stem from the rear of the breaker with the breaker closed The interrupter is satisfactory if the mark on the stem i...

Страница 38: ...000 3000 3 4 7 2 INNER 4 2 INNER VCP W K 1 circuit breaker barrier configurations ANSI breaker identification Amps Reference vacuum interrupter diameter inches Number of barriers 150 VCP W40 1200 2000...

Страница 39: ...e shaft 2 Main link 3 Banana link 4 Trip latch 5 Shunt trip lever 6 Shunt trip coil 7 Cam shaft 8 Closing cam 9 Operating rod 10 Main link roller 11 Trip bar D shaft 12 Trip latch reset spring Figure...

Страница 40: ...ging schematic 1 Pole shaft 2 Anti close interlock 3 Spring release close latch 4 Spring crank 5 Closing spring 6 Closing spring fixed end 7 Spring release close coil 8 Cam shaft 9 Motor ratchet lever...

Страница 41: ...close the circuit breaker In Figure 20c the linkage is shown with the circuit beaker in the closed position before the closing springs have been recharged Interference of the trip D shaft with the tr...

Страница 42: ...lation operation and maintenance of type VCP W vacuum circuit breakers EATON www eaton com Figure 22 Typical VCP W DC and AC control schemes Dashed lines represent customer wiring and components This...

Страница 43: ...ers EATON www eaton com Figure 23 15 kV VCP WXC 63 kA 1200 3000 A special power plant breakers styles 4A35390G10 4A35391G10 4A35392G10 DC control scheme and diagram Dashed lines represent customer wir...

Страница 44: ...LES 4A35390G10 4A35391G10 4A35392G10 CIRCUIT BREAKERS ARE CONFIGURED FOR POWER PLANT SPECIFIC APPLICATIONS ONLY POTENTIALLY SEVERE UNINTENDED CONSEQUENCES COULD RESULT IF THESE DEVICES ARE MISAPPLIED...

Страница 45: ...enal source it will trip the breaker open The shunt trip device is available with rated voltages of 24 Vdc 48 Vdc 125 Vdc 250 Vdc 120 Vac and 240 Vac A cap trip device must be used with the 120 Vac an...

Страница 46: ...operation and maintenance of type VCP W vacuum circuit breakers EATON www eaton com Figure 24 15 kV under voltage trip device configuration 1 Moving clapper 2 Stationary yoke 3 UV trip device coil 4 E...

Страница 47: ...the device is a racking screw racking nut and moving block Although the device is mounted in the switchgear compartment a brief description here will help understand the operation Figures 13 and 15 Fo...

Страница 48: ...d be immediately inspected and the schedule for inspection and maintenance should be re evaluated based upon the inspec tion results Additionally because of the variability of system fault characteris...

Страница 49: ...e is intended as a general guideline and should be applied in conjunction with the experience and good judgment of the individual performing the work m CAUTION OVER TORQUING CAN CAUSE PERMANENT DAMAGE...

Страница 50: ...upter assembly and perform contact wipe check If the bushing is NOT intact then glue back the bushing to the cup plate and observe the mark again Replace interrupter assembly If integrity check is not...

Страница 51: ...CAL CHARGE BEFORE COMING IN CONTACT WITH THE PRIMARY CIRCUIT To avoid any ambiguity in the AChigh potential test due to leakage or displacement capacitive current the test unit should have sufficient...

Страница 52: ...upter showing contact erosion indica tor with breaker closed indicators are checked only when the breaker is closed Figure 29 Wipe indication procedure performed only with the breaker closed Cup plate...

Страница 53: ...r each pole The resistance should not exceed the values shown in Table 25 Table 25 Typical resistance measurements Rated continuous current amperes Resistance microohms 1200 2000 3000 60 40 20 6 9 Mec...

Страница 54: ...sing spring status indicates Discharged and the main contact indicator shows Open Figure 7 2 Remove the circuit breaker front cover Be sure to save the original fasteners for reassembly 3 Cut a piece...

Страница 55: ...g springs 7 Charge the closing springs with the maintenance tool Continue charging the closing springs until a click is heard and the status indicator shows Charged Figure 35 8 While holding the marke...

Страница 56: ...ove the marker from hole C 11 Push the push to open clapper to open the circuit breaker Figure 43 Front view of closure tool showing mounting testing locations 6352C49H01 12 Inspect the circuit breake...

Страница 57: ...e grease with no side effects For breakers built after 1 1 2018 All parts that require lubrication have been lubricated during the assembly with Eaton s new synthetic grease Over a period of time this...

Страница 58: ...latch binding Close latch roller binding Trip circuit energized Undesirably closes Control circuit Close circuit CS C getting shorted Mechanism Close release latch fails to reset Close floor tripper...

Страница 59: ...50 250 2000 A 58 kA 50 250 2000 A 58 kA 5 SC 50 250H 2000 A 78 kA 8297A02H01 8297A02H21 8297A05H01 8297A03H01 8297A03H21 8297A06H01 8297A02H02 8297A02H22 8297A05H02 8297A03H02 8297A03H22 8297A06H02 82...

Страница 60: ...1 000 1200 A 77 kA 5 LT 150 1000C 1200 A 77 kA 5 LT 150 1 000 2000 A 77 kA 7 150 1 000 2000 A 77 kA 5 150 1 000 2000 A 77 kA 5 LT 150 1000C 2000 A 77 kA 5 LT 150VCP W40C 1200 A 1 50VCP W40C 2000 A 150...

Страница 61: ...to 15kV Interphase barriers 2000 A outside Barriers 1200 2000 A 694C549G03 694C549G06 694C549G03 694C549G06 4 Barriers 694C622G03 694C622G03 1 1 36 Up to 15 kV All 50 350 150 1000 150 63 and 3000 A br...

Страница 62: ...3 1 1 1 50 Rectifier 1 20 240 Vac 3759A79G02 3759A79G01 1 1 51 52 53 54 55 Anti pump Y relay 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac 3759A74G03 3759A74G04 3759A74G05 3759A74G01 3759A74G02 8237A27H03 82...

Страница 63: ...01 3759A93G01 699B147H01 3759A93H02 8064A03G01 3759A93G01 1 1 66 Auxiliary switch 698B822H01 5697B02G01 5697B02G02 1 67 Trip D shaft 694C638G02 694C638G02 694C638G02 1 68 Main link trip latch 3A75675G...

Страница 64: ...Typical view VCP WC 101 102 103 Interrupter Assembly 50 25C 1200 A 50 25C 2000 A 50 25C 3000 A 8297A33H01 8297A33H02 8297A33H03 3 3 3 104 105 106 50 40C 1200 A 50 40C 2000 A 50 40C 3000 A 8297A34H01...

Страница 65: ...8299A01H05 3 3 6 7 36 40 1250 A 36 40 2000 A 8299A01H06 8299A01H07 3 3 8 9 10 72 25 630 A 72 25 1250 A 72 25 2000 A 8299A01H08 8299A01H09 8299A01H10 3 3 3 11 12 72 32 1250 A 72 32 2000 A 8299A01H11 8...

Страница 66: ...Up to 17 5 kV 24 kV 28 29 29A 240 25 650 A 240 25 1250 A 240 25 2000 A 8299A01H28 8299A01H29 8299A01H30 3 3 3 30 31 Primary disconnects Up to 175 40 630 A Up to 175 40 1250 A 699B104G01 699B104G01 6...

Страница 67: ...G03 699B196G01 699B196G02 699B196G06 699B196G04 699B196G05 1 1 1 46 Motor brush kit 8063A77G01 8063A77G01 1 47 48 49 Spring release coils 48 Vdc 125 Vdc 120 Vac 250 Vdc 240 Vac 3759A76G01 3759A76G02 3...

Страница 68: ...V trip coils 48 Vdc 125 Vdc 250 Vdc 120 AC 240 AC 8064A19G01 8064A19G02 8064A19G03 8064A19G09 8064A19G08 8064A19G01 8064A19G02 8064A19G03 8064A19G07 8064A19G08 1 1 1 1 1 63 Motor cut off switch 699B19...

Страница 69: ...heel 3617A99G01 3617A99G01 74 Fastener kit 8061A01G01 8061A01G01 75 Labels kit 3759A79G01 8295A45G04 1 76 Wiring harness repair kit complete replacement 691C281G01 691C281G03 691C281G04 691C281G01 691...

Страница 70: ...center wheel on the 27 kV roll on the floor breaker is rotated 180 degrees from the picture shown above to align better with the center of gravity 8 2 Optional automatic manual hybrid secondary for BP...

Страница 71: ...been developed for the BPI pan assembly to reduce the required force to manually rack in a 63 kA or 3 000 A breaker If the customer is using a MR2 system to lever in the breakers then this system is n...

Страница 72: ...contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILIT...

Отзывы: