Instructions for installation, operation,  

and maintenance of medium voltage 

VC-W MR2 (integral racking) 

EATON

 www.eaton.com

Pan configurations

Integrated racking is available for all voltage ratings .  For 5/15 kV and 

27 kV switchgear, there is an optional “Test” position available .  The 

“Test” position is a physically different position in this assembly, 

and the breaker can be racked from “Disconnect” to “Test”, “Test to 

Connect”, or in any other order selected by the operator .  See below 

for what positions are available for each voltage rating .

Voltage 

class (kV)

Breaker  

cell width  

in inches

Breaker  

positions available

Auxiliary 

positions available

5/15 

36.00

Disconnect and Connect

Disconnect and Connect

5/15 

a

36.00

Disconnect, Test, and Connect Disconnect and Connect

26.00

Disconnect and Connect

N/A

27 

36.00

Disconnect and Connect

N/A

27 

b

36.00

Disconnect, Test, and Connect N/A

38 

42.00

Disconnect and Connect

N/A

Optional “Test” position with Breaker Position Indication (BPI) pan only.

Optional “Test” position available with non-arc gear equipped with BPI pan only.

Permissive interlocks

Operational interlock features

There are multiple permissive interlocks features built into the 

controller programming, and error codes are displayed on the 

pendant .  There are three standard permissive interlocks wired for 

every breaker cell with integrated racking and one for every auxiliary 

cell with integrated racking .

Breaker cell specific interlocks:

1. 

Normally closed mechanism-operated compartment (MOC) 

contact wired into the controller programming permissive circuit 

(breaker cell only) .  Part of the E5 error code circuit (see  

Figure 1

) .

a. 

If the MV circuit breaker is closed, this circuit will open and 

the motor will not run .

b. 

This permissive uses only the controller programming to stop 

the motor from being powered on .

2. 

Normally closed MOC contact wired in series with the black 

motor lead (breaker cell only) .  Part of the E2 error code circuit 

(see 

Figure 1

) .

a. 

This wrks the same as the first MOC permissive . 

b. 

Used as a redundant interlock in case the first MOC 

permissive fails .

c. 

This contact breaks the power to the motor for a more 

hardwired permissive . 

Breaker cell and auxiliary cell interlocks:

1. 

Normally closed manual crank permissive switch located on the 

right side of the Lev-in assembly (breaker and auxiliary cell) (see 

Figure 15 

and

 

16

) . Part of the E5 error code circuit (see 

Figure 1

) .

a. 

This permissive is opened if an operator inserts a tool into 

the manual crank of the Lev-in assembly .

b. 

This prevents someone from operating the motor while a 

person is manually racking the MV circuit breaker or auxiliary .

In addition to the permissive contacts mentioned above,  

the controller will accept as many normally closed permissive 

contacts wired in series with permissive #1 and #3 as specified  

(see 

Figure 1

- circuit board wiring points) .

Содержание VC-W MR2

Страница 1: ...Open permissive 9 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking Description Page E6 Communication error 9 E7 No MV device 9 E8 Firmware compatibi...

Страница 2: ...2 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 3: ...source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PA...

Страница 4: ...SC 29649 All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further i...

Страница 5: ...ive interlocks wired for every breaker cell with integrated racking and one for every auxiliary cell with integrated racking Breaker cell specific interlocks 1 Normally closed mechanism operated compa...

Страница 6: ...pass E5 error circuit CAUTION by jumpering terminals 51 to 54 you have defeated the inter lock circuit For troubleshooting move the black mo tor lead on terminal 47 to terminal 44 to bypass E2 error c...

Страница 7: ...the auxiliary pan assembly This lock prohibits an operator from manually inserting a crank into the Lev in assembly and manually racking the breaker or auxiliary device as specified in the switchgear...

Страница 8: ...hen motor current is in excess of allowed value Multiple causes could create this condition E1 error codes may occur if system is operated on temporary generator power Operator should shut off power t...

Страница 9: ...ibility error This state results from the pendant and controller card not having compatible firmware Contact your Eaton representative to have the firmware updated E9 No test MR2 open close only This...

Страница 10: ...Disconnect buttons can be used to scroll up and down 01 to 99 until the desired address number is reached While scrolling the Connect LED will continue to flash to let the user know that the address...

Страница 11: ...device from a distance of up to 30 ft 9 14 m from the equipment with a Cat 5 cable typically there will be an RJ 45 jack located on the front panel of the switchgear see Figure 14 The MV device can b...

Страница 12: ...cking device via a SCADA system or multiple Modbus interface communication systems These systems can be wired to a central control room or to a remote panel located a safe distance away from the equip...

Страница 13: ...ontrol power to breaker a At this time the breaker open and close operations can be tested electrically b To proceed further and rack the breaker to the connected position the breaker must be open 1 A...

Страница 14: ...ator should then open the breaker c After the breaker is open the error can be cleared by pressing the disconnect button 8 Once the error is cleared the operator can rack the breaker to the test or di...

Страница 15: ...15 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com Notes...

Страница 16: ...16 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 17: ...17 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 18: ...n USA Publication No IB022010EN TBG001320 July 2019 Eaton is a registered trademark All other trademarks are property of their respective owners Instructions for installation operation and maintenance...

Отзывы: