Instructional Booklet 

IB022010EN

Effective July 2019
Revision #4

Instructions for installation, operation,  

and maintenance of medium voltage 

VC-W MR2 (integral racking) 

EATON

 www.eaton.com

Option 2

Discrete I/O control allows the user to operate the integral racking 

device via pushbuttons or PLC .  These systems can be wired to a 

central control room or to a remote panel located a safe distance 

away from the switchgear equipment .  If an error occurs while under 

I/O control, all I/O breaker position indication lights will flash .  The 

pendant can then be plugged into the RJ-45 jack located on the front 

panel of the switchgear - (see 

Figure 14

) to read the error code .  

Once the pendant is plugged in, I/O control is disabled until the 

pendant is unplugged .

MR2 5 VDC

20 mA

MR2 O/C 24 VDC

20 mA

**include typical schematics**

Option 3

Modbus communication control allows the user to operate the 

integral racking device via a SCADA system or multiple Modbus 

interface communication systems .  These systems can be wired 

to a central control room or to a remote panel located a safe 

distance away from the equipment .  Error codes can be read with 

the Modbus communication system .  Eaton can supply an installed 

Modbus system or the Modbus addresses to the customer for 

their personalized Modbus system and programming (for Modbus 

Interface details, refer to “1C19667 MODBUS interface  .txt”) .

Figure 14. RJ-45 pendant jack.

Callout descriptions

a

d

f

c

e

g

b

Figure 15. Typical MR2 – standard breaker pan assembly.

1. 

VC-W MR2 motor/controller assembly .

2. 

Manual crank safety permissive switch: disables the motor if an 

operator were to insert a manual tool to rack the circuit breaker .

3. 

“Disconnect” positional limit switch: activated when the circuit 

breaker is in the disconnected position .

4. 

“Connect” positional limit switch: activated when the circuit 

breaker is in the connected position .

5. 

“Test” positional limit switch: activated when the circuit breaker 

is in the “Test” position .

6. 

Limit switch actuator .

7. 

Lev-in lead screw .

Содержание VC-W MR2

Страница 1: ...Open permissive 9 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking Description Page E6 Communication error 9 E7 No MV device 9 E8 Firmware compatibi...

Страница 2: ...2 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 3: ...source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PA...

Страница 4: ...SC 29649 All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further i...

Страница 5: ...ive interlocks wired for every breaker cell with integrated racking and one for every auxiliary cell with integrated racking Breaker cell specific interlocks 1 Normally closed mechanism operated compa...

Страница 6: ...pass E5 error circuit CAUTION by jumpering terminals 51 to 54 you have defeated the inter lock circuit For troubleshooting move the black mo tor lead on terminal 47 to terminal 44 to bypass E2 error c...

Страница 7: ...the auxiliary pan assembly This lock prohibits an operator from manually inserting a crank into the Lev in assembly and manually racking the breaker or auxiliary device as specified in the switchgear...

Страница 8: ...hen motor current is in excess of allowed value Multiple causes could create this condition E1 error codes may occur if system is operated on temporary generator power Operator should shut off power t...

Страница 9: ...ibility error This state results from the pendant and controller card not having compatible firmware Contact your Eaton representative to have the firmware updated E9 No test MR2 open close only This...

Страница 10: ...Disconnect buttons can be used to scroll up and down 01 to 99 until the desired address number is reached While scrolling the Connect LED will continue to flash to let the user know that the address...

Страница 11: ...device from a distance of up to 30 ft 9 14 m from the equipment with a Cat 5 cable typically there will be an RJ 45 jack located on the front panel of the switchgear see Figure 14 The MV device can b...

Страница 12: ...cking device via a SCADA system or multiple Modbus interface communication systems These systems can be wired to a central control room or to a remote panel located a safe distance away from the equip...

Страница 13: ...ontrol power to breaker a At this time the breaker open and close operations can be tested electrically b To proceed further and rack the breaker to the connected position the breaker must be open 1 A...

Страница 14: ...ator should then open the breaker c After the breaker is open the error can be cleared by pressing the disconnect button 8 Once the error is cleared the operator can rack the breaker to the test or di...

Страница 15: ...15 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com Notes...

Страница 16: ...16 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 17: ...17 Instructional Booklet IB022010EN Effective July 2019 Revision 4 Instructions for installation operation and maintenance of medium voltage VC W MR2 integral racking EATON www eaton com...

Страница 18: ...n USA Publication No IB022010EN TBG001320 July 2019 Eaton is a registered trademark All other trademarks are property of their respective owners Instructions for installation operation and maintenance...

Отзывы: