8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Setting the start (date and time) of the
first battery duration test and the intervals
(1 ... 12 months) of subsequent battery
duration tests.
<ok>
Menu 3.4:
Language
Date & time
Functiontest
Durationtest
etc....
Substation
synchronise ?
Menu = no OK = yes
Select the input position for date,
time and interval (in months) with
Change with
Finish with <Menu>
This request follows:
The end of a duration test can be modified
with arrow left, arrow right in the yellow
line:
MEANINGS:
End of duration test = nominal operating duration:
the
duration test runs until the set nominal operating duration,
i.e. 1 h, 2 h, 3 h or 8 h
End of duration test = total discharge protection:
the
duration test runs until total discharge protection (but to
maximum of 99 h and 59 min)
End of duration test = limit operating duration:
the dura-
tion test runs until the set percentage of nominal operating
duration (i.e. 40 minutes at 1 h and 67 %)
With the limit operating duration the evaluation voltage may
also be entered. When therefore battery voltage at the end
of the limit operating duration is lower than the evaluation
voltage, a capacity error is displayed.
If the nominal operating duration is modified in the Series
number and type menu, the preset evaluation voltage also
changes analog to the battery types approved by us. Other
evaluation voltages may also be used via the above-specified
parameters. As such, a duration test to 50% would be fea-
sible, with a correspondingly higher evaluation voltage in
accordance with the battery data sheet.
In the duration test menu the end criterion of the duration
test can be set with the evaluation criterion. This also enables
a duration test with 2/3 (67%) to be carried out, at the end of
which a minimum battery voltage must be available.
The values can only be set on the device, not via CG-Vision
or the PC software.
Duration test end
nom. oper. duration 3h <->
Duration test end
total discharge protection <->
Duration test end
limit oper. duration 67% <->
total discharge protection
U=212,4 V <->
After moving the cursor onto the ‚Duration
test end‘ line and pressing OK, the follo-
wing submenu is displayed:
B-Test Date&Time
We 11.12.07 12:00
Duration test end
Interval in months: 12