URING 12-24-LLC SF6 INSULATED COMPACT RMU SWITCHGEAR WITH VACUUM CIRCUIT BREAKER

The use of lifting beams is required for cubicle assemblies with control boxes as the sole 
exception, slings or chains may be used if the cubicles of the assembly have identical height 
control boxes installed.

• If it is not possible to lift using the mentioned
methods, rollers may be used underneath
the switchgear. Another option is to slide the
cubicles over rods (these same rods can be
used to help get over the cable pit).

• To  handle 5 functional unit assemblies
(consisting  of either coupled modules or
compact assemblies associated with modules),
use lifting systems (slings, lifting beam, etc.)
with a pull  angle  greater  than  65º and less
than 115º in order to prevent possible damage
to the cubicles during hoisting.

Lifting of a set of 3 

URING

 functional units with a forklift truck

Lifting of a set of 5 

URING

 functional units with lifting beam 

and chains

Содержание Ulusoy URING12-24-LLC-SF6

Страница 1: ...Ulusoy URING12 24 LLC SF6 Insulated Compact RMU Switchgear with Vacuum Circuit Breaker User Manual 12 24kV 200 630A 21kA 3s www eaton com...

Страница 2: ...IT BREAKER UNIT 8 2 1 CLOSING THE SWITCHGEAR DOOR 8 2 2 OPENING THE EARTHING SWITCH 8 2 3 CHARGING AND CLOSING THE DISCONNECTOR 8 2 4 CHARGING AND CLOSING THE CIRCUIT BREAKER 8 3 CUTTING CIRCUIT BREAK...

Страница 3: ...sibility of the manufacturer More specifically The equipment must be handled and transported appropriately from the factory to the place of installation All intermediate storage should occur in condit...

Страница 4: ...ust be isolated from the supply voltage Warning Risk of injury from movable parts in mechanical drives Before performing maintenance work Isolate the system from the supply voltage Release the circuit...

Страница 5: ...tly on the ground or on a pallet depending on the type of handling involved To handle assemblies of up to 5 functional units one of the following methods must be used Using a forklift truck or pallet...

Страница 6: ...ed underneath the switchgear Another option is to slide the cubicles over rods these same rods can be used to help get over the cable pit To handle 5 functional unit assemblies consisting of either co...

Страница 7: ...contamination from dust smoke corrosive and or inflammable gases vapours or salt The switchgear must be protected from the rain and the humidity conditions should be as follows o the mean relative hum...

Страница 8: ...g 12 24 LLF is 3 way unit in a single SF6 tank Two incoming outgoing unit with load break switch and one transformer protection unit with fuse combination This is 3 way design Uring 12 24 RMU can be d...

Страница 9: ...Remote Controller Button optional Operating Handle 6 ACCESSORIES Cable Bushings Interface C Cable Clamps Earth Bar...

Страница 10: ...URING 12 24 LLC SF6 INSULATED COMPACT RMU SWITCHGEAR WITH VACUUM CIRCUIT BREAKER 7 DIMENSIONS...

Страница 11: ...cannot be delivered with cells In Output Cells To check cable faults Turn the breaker on Turn the disconnector on Turn the earthing disconnector off Open the cell front cover Place the cable test devi...

Страница 12: ...GEAR DOOR Earthing switch must be closed for closing opening the switchgear door In the first step the door is open load break switch is open and the earthing switch is closed Put the bottom side of t...

Страница 13: ...H Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in open position now Rotate the lever in the...

Страница 14: ...ng charge lever hole and rotate in the direction of arrow Clockwise Push the closing I button to close load break switch If there is DC on the auxilliary contacts turn the manuel motor switch button t...

Страница 15: ...ch must be closed for closing opening the switchgear door In the first step the door is open disconnector switch is open and the earthing switch is closed Put the bottom side of the door to the switch...

Страница 16: ...BREAKER 8 2 2 OPENING THE EARTHING SWITCH Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in op...

Страница 17: ...rrow Clockwise If there is DC on the auxiliary contacts turn the manual motor switch button to the motor selection Then the spring will be automatically charged by the motor Push the closing I button...

Страница 18: ...otate in the direction of arrow Clockwise If there is DC on the auxiliary contacts turn the manual motor switch button to the motor selection Then the spring will be automatically charged by the motor...

Страница 19: ...pening O button to close load break switch Put the key removed from the circuit breaker to disconnector safety lock Push the opening O button to close load break switch Check the position indicator fo...

Страница 20: ...EAKER 8 3 3 CLOSING EARTHING SWITCH Put the lever into the earthing switch lever hole Remove the handle from earthing switch lever hole Check the position of the earthing switch It must be in close po...

Страница 21: ...8 3 4 OPENING THE SWITCHGEAR DOOR Push the door upwards Pull the door towards yourself The door is opened...

Страница 22: ...CLOSING EARTHING SWITCH Push the opening O button to open load break switch Put the lever into the earthing switch lever hole Check the position indicator for open position Rotate the lever in the dir...

Страница 23: ...8 4 3 OPENING THE SWITCHGEAR DOOR Push the door upwards Pull the door The door is opened...

Страница 24: ...URING 12 24 LLC SF6 INSULATED COMPACT RMU SWITCHGEAR WITH VACUUM CIRCUIT BREAKER 9 CABLE CONNECTION 10 OVER PRESSURE FLAP POSITION T connector interface C for incoming outcoming connection...

Страница 25: ...11 COMBINING MODULAR CUBICLES Modular Cubicles are combined by using 6 pieces of M8x30 bolt Prior to assembly silicon crossing bushings and contact holes must be cleaned well...

Страница 26: ...n is to improve the quality of life and the environment through the use of power management technologies and services We provide sustainable solutions that help our customers effectively manage electr...