TriSync Three-Phase Vacuum Capacitor Switch

InstallatIon and operatIon InstructIons

   MN230011EN   January 2023

Product information

Introduction

Service Information MN230011EN provides installation 

instructions, operation information, and maintenance 

information for Eaton’s Cooper Power series TriSync™ 

capacitor switches.
The information contained in this manual is organized 

into the following major categories: Safety information, 

Product information, Ratings and specifications, Installation 

procedure, Switch operation, Dimensions, and Service 

information. Refer to the table of contents for page 

numbers.

Read this manual first

Read and understand the contents of this manual and follow 

all locally approved procedures and safety practices before 

installing or operating this equipment.

Additional information

These instructions cannot cover all details or vari ations 

in the equipment, procedures, or process described nor 

provide directions for meeting every possible contin gency 

during installation, operation, or maintenance. When 

additional information is desired to satisfy a problem not 

cov ered sufficiently for the user’s purpose, please contact 

your Eaton Cooper Power series product representative.

Acceptance and initial inspection

Each capacitor switch is completely assembled, inspected, 

tested, and adjusted at the factory. It is in good condition 

when accepted by the carrier for shipment. Upon receipt of 

a capacitor switch, inspect the capacitor switch thoroughly 

for damage and loss of parts incurred during shipment. If 

damage or loss is discovered, file a claim with the carrier 

immediately.

Handling and storage

If the capacitor switch is to be stored for an appreciable 

time before installation, provide a clean, dry storage area. 

Locate the capacitor switch so as to minimize the possibility 

of mechanical damage. 
When transporting or storing the switch, the contacts 

should be kept in the closed position to avoid damage to 

the vacuum bottle contacts.

Standards

TriSync capacitor switches are designed and tested in 

accordance with IEEE Std C37.66™ standard.

Quality standards

ISO 9001 Certified Quality Management System

Description of operation

The TriSync vacuum capacitor switch is a Three phase, 

Solenoid-operated vacuum switch. The solid polymer 

insulation system does not rely on gas, foam, or liquid 

dielectrics. Highly resistant to ozone, oxygen, moisture, 

contamination, and ultraviolet light, it is an environmentally 

safe capacitor switch. The TriSync capacitor switch has 

polymer bushings and is suitable for operation through a 

temperature range as shown in Table 1.

Содержание TriSync COOPER POWER MN230011EN

Страница 1: ...TriSync Three Phase Vacuum Capacitor Switch Installation and Operation Instructions COOPER POWER SERIES Vacuum Switches MN230011EN Effective January 2023 New issue...

Страница 2: ...ICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUME...

Страница 3: ...initial inspection 1 Handling and storage 1 Standards 1 Quality standards 1 Description of operation 1 RATINGS AND SPECIFICATIONS 2 Check switch ratings before installation 2 Ratings 2 INSTALLATION PR...

Страница 4: ...us situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indica...

Страница 5: ...epresentative Acceptance and initial inspection Each capacitor switch is completely assembled inspected tested and adjusted at the factory It is in good condition when accepted by the carrier for ship...

Страница 6: ...t A 6 000 6 000 12 500 Withstand peak current A 15 000 15 000 32 500 Short time symmetrical withstand current A 4 500 4 500 6 250 High frequency transient making peak current A 9 000 12 000 9 000 10 0...

Страница 7: ...quipment Failure to comply can result in death severe personal injury and equipment damage T223 2 WARNING This equipment is not intended to protect human life Follow all locally approved procedures an...

Страница 8: ...s are shown in Figure 3 Accessories are shown with dashed lines These diagrams apply only for alternating current ac control voltage For direct current dc control voltage please contact your Eaton s C...

Страница 9: ...Switch Coil Interrupting Switch Indirect Auxiliary Switch Direct Auxiliary Switch Direct Auxiliary Switch D 6 Pin Three Wire Control with Form C Auxillary Switch Accessory H 10 Pin Three Wire Control...

Страница 10: ...to follow proper safety practices can result in contact with high voltage which will cause death or severe personal injury G112 1 The TriSync switch features a manual gang open operation operating all...

Страница 11: ...X XXX 01 X 1 TITLE DESC DWG DATE REF SHEET PGR 11 4 2021 SCALE OF 2 5 THIS DRAWING HAS BEEN GENERATED FROM A 3D MODEL ECS 3 Phase Frame 25kV ECS 25 kv 3 Phase Switch and Frame assembly 150 BIL 3 Phase...

Страница 12: ...enance however the switch should be inspected on a regular basis to check for physical damage and to verify operation Frequency of inspection Because these switches are applied under widely varying op...

Отзывы: