7. UPS maintenance
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment
clean and dust free. If the atmosphere is very dusty, clean the outside of the
system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C
(77°F).
If the UPS requires any type of transportation, verify that the UPS is
disconnected and turned off. The batteries are rated for a 3-5 year service life.
The length of service life varies, depending on the frequency of usage and
ambient temperature. Batteries used beyond expected service life will often
have severely reduced runtimes. Replace batteries at least every 4 years to keep
units running at peak efficiency.
7.2 Transporting the UPS
Please transport the UPS only in the original packaging (to protect against shock
and impact).
7.3 Storing the equipment
If you store the equipment for a long period, recharge the battery every 6
months by connecting the UPS to utility power. The EBM charge to 90% capacity
in less than 3 hours.
However, recommends that the batteries charge for 48 hours after long-term
storage.
If the date has passed and the batteries were never recharged, do not use them.
Contact your service representative.